10. Operating Modes
10.1 Static-Bypass (Stop operation)
If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched
from the unit’s main circuit to the bypass circuit. Power flow through the bypass is shown in the following
illustration. This change-over occurs automatically in phase in less than one-quarter cycle of the input
waveform. The switching period is not long enough to cause interruptions to occur in most loads.
•
If the power flow is transferred to the bypass circuit due to an internal fault the UPS will continue to
supply power to the load through the bypass and indicate a system fault message (see
•
If the power flow is transferred to the bypass circuit due to an overload condition (see “24.4 System
Warning Messages” on page 54), then the power flow will automatically transfer from the UPS’s
bypass circuit back to the inverter circuit after removing the overload if set to do so (AutoXfer
parameter (Cmd ID 660)).
10.2 On-Line (Run operation)
The following illustration shows circuit power flow when the UPS is operating normally in the
On-Line
mode. The UPS rectifier, including a boost chopper circuit, converts AC input power to DC power. The
boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries. The
inverter section generates a high quality sinu soidal output voltage. The unit’s batteries are always
maintained in a constantly charged state when the UPS is in the run operation mode.
Output
Power
Line Filter
Inverter
*Static Switch
Isolation
Transformer
Input
Power
Input
Fuse
Power Flow
Bypass
* Switches are
solid state
devices.
MCCB
Output
Fuse
Surge
Absorber
Batteries
+
–
Rectifier/
Chopper
POWER FLOW IN ON-LINE MODE FOR ALL MODELS
Negative Bus
POWER FLOW IN BYPASS FOR ALL MODELS
Output
Power
Line Filter
Inverter
*Static Switch
Isolation
Transformer
Input
Power
Input
Fuse
Power Flow
Bypass
* Switches are
solid state
devices.
MCCB
Output
Fuse
Surge
Absorber
Batteries
+
–
Rectifier/
Chopper
Negative Bus
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......