1600XP/XPi Series Installation and Operation Manual – 60616-012
10.5 Battery Backup Time and Discharge Process
The UPS internal batteries provide approximately 5-7 minutes of back-up time depending on the 1600XP/
1600XPi unit kVA rating. These times are valid when the unit is operating under full load and at the
rated power factor. The exact length of these times will depend on the UPS model used, condition of
the batteries, amount and type of load, temperature and other variables. See battery backup time in
“Appendix A: 1600XP/1600XPi Specifications” on page A1
.
The following illustration graphically shows the battery discharge process at full load conditions.
10.6 Battery Low Voltage Tolerances
Excessive discharge will cause the UPS battery voltage to drop. The chart shown below lists the voltage
level at which each UPS low-voltage alarm will sound and at what level the low-voltage condition will
cause the unit to automatically shut down.
UPS Capacity
3.6 kVA
6 kVA
8 kVA
10 kVA 14 kVA 18 kVA
22 kVA
Nominal voltage (Vnom)
144 Vdc 216 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc
Alarm voltage (Vlow)
130 Vdc 192 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc 246 Vdc
Shutdown voltage (Vmin)
114 Vdc 170 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc 227 Vdc
BATTERY CAPACITY
SHUTDOWN
I
MAX
I
MIN
V
NOM
V
LOW
V
MIN
100%
20% 0%
CURRENT VOLTAGE
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......