25
1600XP/XPi Series Installation and Operation Manual – 60616-012
13. LCD Touchscreen Layout
The touchscreen serves as input and display. Touch the active portion of the display to execute a com-
mand.
13.1 Startup Display
The default opening screen for the UPS is the
Main
screen. The operator can begin operating the UPS
immediately by pressing the RUN key.
Only the
Main
and
Settings
tab screens allow operator input. The
Monitor
and
Records
display screens
are read-only. No data can be entered in these screens
From the
Main
screen, the UPS can be placed On-Line by pressing RUN, or placed in Bypass Mode by
pressing STOP. A key status indicator at the upper right-hand corner of each key indicates which key is
active: a dot indicates that key is active; no dot indicates that key is not active. See the illustration below.
The
Settings
screen allows modification of the UPS operating parameters.
At the top of the display are four status indicators: % Load, Battery Information, UPS System Status, and
System Time.
At the top left of the display are a bank of four touch-sensitive keys:
Home – Pressing
HOME
key returns the display to the top menu of the currently selected tab.
Security Level – Pressing the
Security Leve
l key activates the log-in security screen.
(Speaker) – Pressing the
Speaker
key will disable/enable the audible alarm.
Touchscreen Lock – Locks touchscreen except for this key.
LCD TOUCHSCREEN
DISPLAY LAYOUT
UPS System Status
Warning Code
UPS
System
Mode
Fault Code
12-Hour
Clock
Security Level: USR
–
User
ADM
–
Administrator
Function Tabs
Home Page
RUN key
STOP key
On-Line
DVCOH
ASYN
1600
XP
On-Line UPS
UPS Serial Number
20080112345
UPS Typeform
UXPB2B100C6
RUN
STOP
UPS Controls
Speaker
On/Off
Main
Monitor
Settings
Records
12:35 PM
INV
HOME
USR
Touchscreen lock
96%
100%
% FullLoad
Battery Information
Key Status Indicator
(UPS is in On-Line mode)
Key Status Indicator
(UPS is NOT in Bypass
mode)
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......