A1
1600XP/XPi Series Installation and Operation Manual – 60616-012
Appendix A: 1600XP/1600XPi Specifications
Standard Model: 3.6 – 10 kVA
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
General
Typeform
UH3G2L036C61T
H3BG2L036C61T
UH3G2L060C61T
H3BG2L060C61T
UH3G2L080C61T
H3BG2L080C61T
UH3G2L100C61T
H3BG2L100C61T
Certifications
ANSI C62.41 (IEEE 587), UL 1778, CUL, CE, FCC Class A , NEC (NFPS-70), NEMA/
PE1-1993, OSHA, ASME, ISO 9001, ISO 14001:2004 , RoHS Compliant
Input Characteristics
Input Voltage
1
Single-phase, 208/240 Vac, +10%
1,4
(to -30% at typical 70% load)
Input Frequency
45 – 65 Hz (auto-sensing)
Input Capacity
3.6 kVA
6 kVA
8.0 kVA
10 kVA
Input /(Max Input) Current @208V
17.9 (18.7) A
29.8 (31.1) A
38.9 (40.5) A
48.6 (50.2) A
Input/(Max. Input) Current @240V
15.5 (16.2) A
25.9 (27.0) A
33.7 (35.1) A
42.1 (43.5) A
Input Power Factor
0.98 Typical, 0.95 Minimum@ 100% Load
Current THD (linear load)
< 5% total harmonic distortion
Internal AC Input Breaker Rating
30 A/277 V
50 A/277 V
60 A/277 V
63 A/277 V
Battery Characteristics
Battery Type
Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged @ 0.7
power factor, 77 °F
8 min.
2
8 min.
2
7 min.
2
7 min.
2
Backup time, fully charged @ 0.85
power factor, 77 °F
7 min.
2
7 min.
2
7 min.
2
5 min.
2
Recharge Time
24 hr. (full), 12 hr. (90%) for internal batteries only
3
Battery Voltage (Nominal)
144 Vdc
216 Vdc
288 Vdc
Output Characteristics
Output Voltage
Single-phase, 240/208/120 V
Output Voltage Regulation
= ± 3%
Output Frequency
±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
AUTO/MAN Frequency
Factory or authorized service center selectable only
Voltage THD
< 3% for linear load; < 6% for non-linear load
Common-Mode Noise
< 0.5 Vrms
Rated Load Power Factor
1
0.85 (0.6 – 1.0) lagging
Efficiency (ac-dc-ac)
≥83%
>85%
Voltage Transient
< ±8% (Load of 0 – 100 %)
Voltage Transient Recovery
50 ms to within 2% of nominal
Rated Output Current (rms)
15 A
25 A
33.3 A
41.6 A
Max Peak Output Current
45 A
75 A
100 A
125 A
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3.
An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4.
If Vin is below the minimum Vin window, the UPS goes to Battery Mode. If the UPS is in Fault and Vin is below the minimum
Vin window, the UPS goes to Bypass Mode
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......