A5
1600XP/XPi Series Installation and Operation Manual – 60616-012
STANDARD MODELS: 14 – 22 KVA (CONT’D)
1.
nput/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3% per additional 1000 feet elevation.
3.
Subject to update without notice.
4.
Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.
Capacity
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1, 5
Max Peak Output Current
174 A
225 A
275 A
Inverter Overload Capacity
125%-30 sec./150%-10 sec
Bypass Overload Capacity
125%-10 min./1000%-1 cycle
Crest Factor
3.0
Environment
Operating Temperature 59 – 77 °F
(15 – 25 °C) Recommended
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
Storage Temperature
-4 – 104 °F (-20 – 40 °C)
Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
Operating Humidity
30 – 90% (no condensation)
Altitude
< 6600 ft. (2000 m) above sea level
2
Acoustical Noise
50 dB (A) maximum @ 1 meter from front panel
Heat Generation (Typical)
6610 BTU/Hr
3
8499 BTU/Hr
3
10,387 BTU/Hr
3
Operation Diagnosis
Battery Check
Performed on start up, by schedule, on-demand (user configurable)
Input OV Protection
Standard
Battery Lifetime
UPS calculates battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps)
Internal Temperature
UPS gives indication of internal temperature, alarm when high temp
Event Data Storage Registers
32 – Operation, 32 – Backup, 32
–
Warnings, 32 – Faults, 32
–
Test,
32
–
System
Applications
Switches
Generator compatible
Bypass Switch
Bypass Disable
Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)
Automatic Retransfer
Factory or authorized service center selectable only
Interface/Communications
Real Time clock
Real Time Clock with backup Lithium Ion Battery
Schedule Operation
Schedule ON/OFF operation of UPS using optional RemotEye III
communication software
Autostart
Automatic UPS Startup when AC is applied – Option can be enabled or
disabled at user’s discretion
Remote ON/OFF
Standard – External terminal
LED Display
3 LED’s indicating On-Line/Fault, Warning, and A/C Input
Operator Interface
Interactive Touchscreen
Buzzer Volume
Standard (Fixed Volume)
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......