B-4
1600XP/XPi Series Installation and Operation Manual – 60616-012
11
4
Input Undervoltage W
arning
Detection Level
VIUV DeLevel
-
-
-
R/W
R/W
66 %
Input Under V
oltage Error detection level setup in
percentage.
Range: 0-100%
11
5
Input Undervoltage W
arning
Recovery Level
VIUV ReLevel
-
-
-
R/W
R/W
70 %
Input Under V
oltage Error recovery level setup in
percentage.
Range: 0-100%
11
6
Input Undervoltage Gradient
VIUV Gradient
-
-
-
R/W
R/W
6
one of the properties to calculated input Under V
oltage
detection and recovery level.
Range: 0-50
11
7
Input Undervoltage
Hysteresis
VIUV Hysteresis
-
-
-
R/W
R/W
8
one of the properties to calculated input Under V
oltage
detection and recovery level.
Range: 0-100%
11
8
Input Undervoltage
Section
VIUV Section
-
-
-
R/W
R/W
230
One of the properties to calculated input Under V
oltage
detection and recovery level.
Range: 0 – 300
11
9
Input Overvoltage W
arning
Detection Level
VIOV DeLevel
R
R
R
R/W
R/W
274
Input Over V
oltage Error detection level.
Range: 100 – 500
Units: V
rms
120
Input Overvoltage W
arning
Recovery Level
VIOV ReLevel
R
R
R
R/W
R/W
264
Input Over V
oltage Error recovery level.
Range: 100 – 500
Units: V
rms
121
Input V
oltage Gain
(T
otal)
Vin Gain
-
-
-
R/W
R/W
6720
Used this value to convert
AD value to actual unit.
Range: 1 – 32767
122
Input V
oltage Of
fset
(T
otal)
Vin Of
fset
-
-
-
R/W
R/W
0
Feedback Of
fset adjustment due to hardware
components and software
AD converter
’s of
fset.
Ramge: -32767 – 32767
123
Input V
oltage
AD
Amount
(T
otal)
Vin
AD
-
-
-
R
R
0
AD summation of 16 samples per half cycle.
124
Input Current Gain
(T
otal)
Iin Gain
-
-
-
R/W
R/W
4897
Used this value to convert
AD value to actual unit.
Range: 1 – 32767
125
Input Current Of
fset
(T
otal)
Iin Of
fset
-
-
-
R/W
R/W
0
Feedback Of
fset adjustment due to hardware
components and software
AD converter
’s of
fset.
Range: -32767 – 32767
126
Input
Current AD Amount
(T
otal)
Iin AD
-
-
-
R
R
0
AD summation of 16 samples per half cycle.
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......