B-5
1600XP/XPi Series Installation and Operation Manual – 60616-012
127
Input Current 100%
Amount
Iin 100%
Amount
-
-
-
R/W
R/W
250
Range: 1 – 1500
Units: dA
128
Input Current Reference Phase Adjustment*
Iref
Phase Adj*
-
-
-
R/W
R/W
14800
Time delay adjustment to sync the phase of input voltage and current due to hardware and software delay
.
(Restart Required)
Range: 0 – 32767
Units: duS
129
Input Undervoltage W
arning
Detection Delay
VIUV DeDelay
-
-
-
-
R/W
1
Input Under V
oltage Error detection delay in
consecutively
.
Range: 0 – 600
Units: 1/2 Cyc
130
Input Undervoltage W
arning
Recovery Delay
VIUV ReDelay
-
-
-
-
R/W
8
Input Over V
oltage Error recovery delay in consecutively
Range: 0 – 600
Units: 1/2 Cyc
131
Input Overvoltage W
arning
Detection Delay
VIOV DeDelay
-
-
-
-
R/W
1
Input Under V
oltage Error detection delay in
consecutively
Range: 0 – 600
Units: 1/2 Cyc
132
Input Overvoltage W
arning
Recovery Delay
VIOV ReDelay
-
-
-
-
R/W
8
Input Over V
oltage Error recovery delay in consecutively
Range: 0 – 600
Units: 1/2 Cyc
133
Input Frequency W
arning
Detection Delay
FIERR DeDelay
-
-
-
-
R/W
4
Input Frequency Error detection delay in consecutively
Range: 0 – 300
Units: 1 Cyc
134
Input Frequency W
arning
Recovery Delay
FIERR ReDelay
-
-
-
-
R/W
8
Input Frequency Error recovery delay in consecutively
Range: 0 – 300
Units: 1 Cyc
135
Input V
oltage in percentage
Input V
oltage(%)
R
R
R
R
R
0
Ratio of input voltage to rated input voltage.
Units: %
136
Input Current in percentage
Input Current(%)
R
R
R
R
R
0
Ratio of input current to rated input current.
Units: %
137
Calculated Input Undervoltage
W
arning Detection Level
VIUV DeLevel
R
R
R
R
R
0
UPS calculates input voltage detection level according
to output power (W) percentage, Gradient, Section and
Rated values.
Units: V
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......