B-6
1600XP/XPi Series Installation and Operation Manual – 60616-012
138
Calculated Input Undervoltage
W
arning Recovery Level
VIUV ReLevel
R
R
R
R
R
0
UPS Calculates input voltage recovery level according to detection level and hysteresis.
Units: V
139
Rated
Active Input Power (W)
Rated InPower(W)
R
R
R
R
R
0
UPS calculates at the startup according to typeform,
efficiency and rated power factor
.
Units: W
141
Input Frequency Setup in Case of Input Frequency Detection Error*
Freq on FIERR*
R
R/W
R/W
R/W
R/W
6000
This frequency setup is used after UPS could not determine input frequency in 3 Seconds.
Then UPS
determine output frequency according to DIP
Switch or
EEPROM setup.
Range: 500 – 600
Units: dHz
201
Output Power Supply
Configuration
Output Config
R
R
R
R
R
0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording
features. Range:
0 – 15
202
Number of Output Lines
No of Output Line
R
R
R
R/W
R/W
1
Range: 1 – 2
203
Output V
oltage
(T
otal)
Output V
oltage
R
R
R
R
R
0
Units: V
rms
204
Output Current
(T
otal)
Output Current
R
R
R
R
R
0
Units: 0.1
Arms
205
Output Frequency
(T
otal)
Output Frequency
R
R
R
R
R
0
Calculated only at Bypass mode and inverter mode. Set to zero for other modes.
Units: 0.1 Hz
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......