B-12
1600XP/XPi Series Installation and Operation Manual – 60616-012
317
Bypass Overvoltage W
arning
Detection Level
VBypOV DeLevel
R
R
R
R/W
R/W
284
Range: 0 – 500
Units: V
318
Bypass Overvoltage W
arning
Recovery Level
VBypOV ReLevel
R
R
R
R/W
R/W
274
Range: 0 – 500
Units: V
320
Bypass Overload Fault
Detection Delay at 125% @ 25
0
C
BypOL
DeDelay
-
-
-
R/W
R/W
600
Range: 0 – 1000
Units: sec
339
Bypass Undervoltage Detection Delay
VBypUV DeDelay
-
-
-
-
R/W
1
Range: 0 – 600
Units: 1/2 cyc
340
Bypass Undervoltage Recovery Delay
VBypUV ReDelay
-
-
-
-
R/W
128
Range: 0 – 600
Units: 1/2 cyc
341
Bypass Overvoltage Detection Delay
VBypOV DeDelay
-
-
-
-
R/W
1
Range: 0 – 600
Units: 1/2 cyc
342
Bypass Overvoltage Recovery Delay
VBypOV ReDelay
-
-
-
-
R/W
128
Range: 0 – 600
Units: 1/2 cyc
343
Bypass Frequency Error Detection Delay
FBypERR DeDelay
-
-
-
-
R/W
4
Range: 0 – 300
Units: cyc
344
Bypass Undervoltage Detection Delay
FBypERR ReDelay
-
-
-
-
R/W
128
Range: 0 – 300
Units: cyc
401
DC Bus V
oltage
(T
otal)
DC Bus
Total
R
R
R
R
R
0
Units: Vdc
402
DC Bus V
oltage
(Positive)
DC Bus Positive
R
R
R
R
R
0
Units: Vdc
403
DC Bus V
oltage
(Negative)
DC Bus Negative
R
R
R
R
R
0
Units: Vdc
404
Rated DC Bus V
oltage
Rated DC Bus
R
R
R
R/W
R/W
770
Range: 200 – 800
Units: Vdc
405
DC Bus Overvoltage Fault Detection Level Percentage
DCOV DeLevel
-
-
-
R/W
R/W
11
0
Range: 80 – 120
Units: %
406
DC Bus Undervoltage Fault Detection Level Percentage
DCUV DeLevel
-
-
-
R/W
R/W
83
Range: 0 – 100
Units: %
409
DC Bus Imbalance Fault Detection Level Percentage
DCIB DeLevel
-
-
-
R/W
R/W
11
Range: 0 – 50
Units: %
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......