B-13
1600XP/XPi Series Installation and Operation Manual – 60616-012
415
Vdc Gain (Positive)
VdcP
Gain
-
-
-
R/W
R/W
7947
Used this value to convert
AD value to actual unit.
Range: 1 – 32767
416
Vdc Of
fset (Positive)
VdcP
Of
fset
-
-
-
R/W
R/W
0
Feedback Of
fset adjustment due to hardware
components and software
AD converter
’s of
fset.
Range: -32768 – 32767
417
Vdc
AD
Amount (Positive)
VdcP
AD
-
-
-
R
R
0
AD summation of 16 samples per half cycle
418
Vdc Gain (Negative)
VdcN Gain
-
-
-
R/W
R/W
7947
Used this value to convert
AD value to actual unit.
Range: 1 – 32767
419
Vdc Of
fset (Negative)
VdcN Of
fset
-
-
-
R/W
R/W
0
Feedback Of
fset adjustment due to hardware
components and software
AD converter
’s of
fset.
Range: -32768 – 32767
420
Vdc
AD
Amount (Negative)
VdcN
AD
-
-
-
R
R
0
AD summation of 16 samples per half cycle
430
DC Bus Slew Rate
DC Bus Slew Rate
-
-
-
-
R/W
5
Range: 0 - 100
431
DC Bus Soft charging time
SoftCharge T
ime
-
-
-
R/W
R/W
360
Range: 0 - 1200
432
DC Bus Hard charging time
HardCharge
Time
-
-
-
R/W
R/W
120
Range: 120 - 1200
436
Calibrated DC Bus Reference
Calibrated DCRef
-
-
-
R/W
R/W
100
Starts from DC Bus reference and slowly ramp up to
this final target value. DC Bus and this value is inversely
proportional.
437
Present DC Bus Reference
Present DCRef
-
-
-
R
R
0
Presently plotting DC Bus reference
438
ACDC Reference
AC/DC Ref
-
-
-
R/W
R/W
288
Range: -310 to 310
439
Input Current Reference Of
fset
Adjustment
Ii Ref Of
fset
-
-
-
R/W
R/W
0
Range: -96 to 96
440
DC undervoltage detection delay
DCUV SW
DeDelay
-
-
-
R/W
R/W
2
Range: 1-32
441
DC overvoltage detection delay
DCOV SW
DeDelay
-
-
-
R/W
R/W
2
Range: 1-32
442
DCUB Detection Delay
DCUB SW
DeDelay
-
-
-
R/W
R/W
2
Range: 1-32
501
Battery V
oltage
Battery V
oltage
R
R
R
R
R
0
Units: Vdc
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......