B-16
1600XP/XPi Series Installation and Operation Manual – 60616-012
548
Charger Reference (Preventive Charging Mode)
Charger Ref(Prev)
-
-
-
R/W
R/W
150
Range: 0 – 320
549
Present Charger Reference
Charger Ref
-
-
-
R
R
0
Presently plotting charger reference
550
Charger Overvoltage Detection Level
CHRGOV DeLevel
-
-
-
R/W
R/W
11
7
Range: 100 – 150
Units: %
551
Charger Overvoltage warning detection delay
CHRGOV W
rnDeDelay
-
-
-
R/W
R/W
8
Range: 1 – 240
Units: 1/2 Cyc
552
Charger Overvoltage warning recovery delay
CHRGOV W
rnReDelay
-
-
-
R/W
R/W
1
Range: 0 – 59
Units: Sec
553
Charger Overvoltage fault detection delay
CHRGOV
FltDeDelay
-
-
-
R/W
R/W
1
Range: 1 – 120
Units: Min
554
Enable Charger controller
En ChrgCtler
-
-
-
R/W
R/W
1
0: Disable
1: Enable
555
Restart Charger controller
Restart ChrgCtler
-
-
-
R/W
R/W
0
0: Disable
1: Enable
556
Batttery Current Multiplier
Ibatt Multiplier
-
-
-
R/W
R/W
12
Range: 1 – 255
557
Of
fset amp hour at 1 C
discharge rate
Of
fset
AH Cap 1
-
-
-
R/W
R/W
22
Range: 0 – 255
558
Of
fset amp hour at 2 C
discharge rate
Of
fset
AH Cap 2
-
-
-
R/W
R/W
29
Range: 0 – 255
559
Of
fset amp hour at 3 C
discharge rate
Of
fset
AH Cap 3
-
-
-
R/W
R/W
36
Range: 0 – 255
560
Of
fset amp hour at 4 C
discharge rate
Of
fset
AH Cap 4
-
-
-
R/W
R/W
39
Range: 0 – 255
561
Battery V
oltage at 1 C
Discharge Rate
BattV at C Rate 1
-
-
-
R/W
R/W
120
Range: 1 – 255
562
Battery V
oltage at 2 C
Discharge Rate
BattV at C Rate 2
-
-
-
R/W
R/W
11
8
Range: 1 – 255
563
Battery V
oltage at 3 C
Discharge Rate
BattV at C Rate 3
-
-
-
R/W
R/W
11
4
Range: 1 – 255
564
Battery V
oltage at 4 C
Discharge Rate
BattV at C Rate 4
-
-
-
R/W
R/W
11
3
Range: 1 – 255
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......