B-19
1600XP/XPi Series Installation and Operation Manual – 60616-012
571-5
Charger Over V
oltage Level
BC CH OV Lvl
-
-
R
R/W
R/W
Set charger overvoltage limit.
This should be atleast 5%
higher than float votlage. To Set 343 V
, enter 3430.
This parameter af
fect both battery cabinet.
Range: 0 – 4000
571-7
Ambient
Over T
emperature
Level
Over T
emp
Lvl
-
-
R
R/W
R/W
Range: 0 – 100
571-8
Over Charge Current Level
Over Ch I Lvl
-
-
R
R/W
R/W
Set Charger overcurrent limit.
This should be 0.8
Amp
above allowed current at full discharge mode. (Prameter
571-10)
To Set 3.8
Amp, enter 380.
This parameter af
fect both battery cabinet.
Range: 0 – 5000
571-9
Constant V
oltage Detection
Level
CV Detect Lv
-
-
R
R/W
R/W
Set 3270 for 327 V float votlage Range: 0 – 4000
571-10
Constant Current Detection Level
CC Detect Lvl
-
-
R
R/W
R/W
Set 300 for 3.00
Amp current limit
Range: 0 – 4000
571-1
1
Number of Current Sense
No Of I Sense
R
R
R
R/W
R/W
Set 2, if two strings are parallel in battery cabinet.
Set 3, if three strings are parallel in battery cabinet.
Range: 0 – 4
571-12
Clear External Battery Cabinet Fault
Clr Ext BC Fault
-
-
R
R/W
R/W
Range: 0 – 5
572-2
Battery Cabinet 1 Input Voltage Calibration Factor
BC1 IP
V GCali
-
-
R
R/W
R/W
Ask Factory for Calibration Procedure.
Range: 0 – 5000
572-3
Battery Cabinet 1 Output Voltage Calibration Factor
BC1 OP
V GCali
-
-
R
R/W
R/W
Range: 0 – 5000
572-4
Battery Cabinet 1
Total Charge
Current Calibration Factor
BC1
Tot I GCali
-
-
R
R/W
R/W
Range: 0 – 1000
572-5
Battery Cabinet 1 Input Voltage of
fset Calibration
BC1 IP
V Ocali
-
-
R
R/W
R/W
Range: -1000 – 1000
572-6
Battery Cabinet 1 Output Voltage of
fset Calibration
BC1 OP
V Ocali
-
-
R
R/W
R/W
Range: -1000 – 1000
572-7
Battery Cabinet 1 Current
of
fset Calibration
BC1
Tot I Ocali
-
-
R
R/W
R/W
Range: -1000 – 1000
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......