D1
1600XPi Series UPS Installation and Operation Manual – 60616-014
Appendix D: Battery Backup Tables (Internal & External Battery Cabinets)
3.6kVA – H3BG2L036C61T
(Runtimes are approximate)
UPS ESTIMATED RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings
Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
1
144
72
3.6
0.85
240
15.00
0.20
612
12
1
144
48
3.6
0.85
240
15.00
0.30
918
12
1
144
33
3.6
0.85
240
15.00
0.40
1224
12
1
144
23
3.6
0.85
240
15.00
0.50
1530
12
1
144
18
3.6
0.85
240
15.00
0.60
1836
12
1
144
14
3.6
0.85
240
15.00
0.70
2142
12
1
144
12
3.6
0.85
240
15.00
0.80
2448
12
1
144
10
3.6
0.85
240
15.00
0.90
2754
12
1
144
9
3.6
0.85
240
15.00
1.00
3060
12
1
144
7
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 1
MATCHING
BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings
Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
4
144
240
3.6
0.85
240
15.00
0.20
612
12
4
144
150
3.6
0.85
240
15.00
0.30
918
12
4
144
112
3.6
0.85
240
15.00
0.40
1224
12
4
144
98
3.6
0.85
240
15.00
0.50
1530
12
4
144
82
3.6
0.85
240
15.00
0.60
1836
12
4
144
70
3.6
0.85
240
15.00
0.70
2142
12
4
144
60
3.6
0.85
240
15.00
0.80
2448
12
4
144
55
3.6
0.85
240
15.00
0.90
2754
12
4
144
50
3.6
0.85
240
15.00
1.00
3060
12
4
144
45
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 2
MATCHING
BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings
Nominal
Runtime
3.6
0.85
240
15.00
0.10
306
12
7
144
300
3.6
0.85
240
15.00
0.20
612
12
7
144
240
3.6
0.85
240
15.00
0.30
918
12
7
144
180
3.6
0.85
240
15.00
0.40
1224
12
7
144
150
3.6
0.85
240
15.00
0.50
1530
12
7
144
120
3.6
0.85
240
15.00
0.60
1836
12
7
144
112
3.6
0.85
240
15.00
0.70
2142
12
7
144
98
3.6
0.85
240
15.00
0.80
2448
12
7
144
90
3.6
0.85
240
15.00
0.90
2754
12
7
144
82
3.6
0.85
240
15.00
1.00
3060
12
7
144
72
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......