F1
1600XPi Series UPS Installation and Operation Manual – 60616-014
Appendix F: External Battery Cabinets (Non-Matching)
F.1 Estimated Runtime
Non-matching battery cabinets are available in a variety of sizes to match your back-up needs. Table F-1 lists the estimated backup time for each UPS
model battery cabinet selections available for each 1600XPi model.
Each of the battery cabinets listed below comes with:
•
6 foot long DC power cables with UPS-specific keyed Anderson plugs.
•
6 foot long A/C Battery Charging cables requiring a L6-30R wall receptacle.
TABLE F-1 - ESTIMATED BACKUP TIMES AT RATED LOAD FOR ONE (1) NON-MATCHING BATTERY CABINET
kVA
P/N
Est. Run Time
(Mins.)*
Battery Cabinets
BC
Breaker
Est. Recharge time
(Hrs.)
Total Wt.
(lbs)
Qty
Style
3.6
H3B13600146EDE1TP
146
1
25T
40A
10.5
1175
H3B13600205EDE1TP
205
1
25T
40A
14.7
1415
H3B13600266EDE1TP
266
1
25T
40A
19.1
1691
6
H3B16000126EDI1TP
126
1
25T
40A
13.1
1535
H3B16000252EDI1BP
252
1
39T
50A
25.1
2408
8
H3B18000126EDI1TP
126
1
25T
40A
13.1
1895
H3B18000252EDI1BP
252
1
39T
50A
25.1
3044
10
H3B1010K138EDI1BP
138
1
25T
50A
14.0
2375
H3B1010K187EDI1CP
187
1
39T
60A
24.4
3044
H3B1010K268EDI2CP
268
2
25T
60A
33.3
4318
14
H3B1014K116EDI1CP
116
1
39T
60A
19.1
2972
H3B1014K213EDI2CP
213
2
25T
60A
33.5
4750
H3B1014K273EDI2CP
273
2
39T
60A
46.8
5944
18
H3B1018K67EDI1VP
67
1
25T
80A
12.4
2375
H3B1018K133EDI2VP
133
2
25T
80A
29.8
4318
H3B1018K220EDI2VP
220
2
39T
80A
46.1
6088
H3B1018K320EDI3TP
320
3
39T
40A
75.9
8916
22
H3B1022K70EDI1EP
70
1
39T
100A
17.6
2972
H3B1022K104EDI2EP
104
2
25T
100A
29.1
4318
H3B1022K199EDI3BP
199
3
25T
50A
47.7
7125
H3B1022K261EDI3BP
261
3
39T
50A
68.8
8916
* Runtime will vary due to differences in battery manufacture, age, temperature, load, life-cycle, and utilization profile.
Notes:
•
Additional runtime can be achieved by
adding additional battery cabinets. Contact your Toshiba representative for details.
•
Estimated runtime and SOC on LCD will be not accurate with non-matching type battery cabinet,
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......