1600XPi Series UPS Installation and Operation Manual – 60616-014
2 Equipment Warning Labels
The following pages show examples of warning
labels that may be attached to either the interior or exterior of the UPS. Do
not remove or cover any of the labels. If the labels are damaged or if additional labels are required, contact your equipment
representative for additional labels.
These labels are placed to provide useful information or to indicate an imminently hazardous situation that may result in
severe equipment/property damage, serious injury, or loss of life if instructions are not followed.
P/N 63094 – External warning sign.
• Unit contains potentially dangerous voltages.
• Read the instruction manual before operating.
• There are no user serviceable parts inside.
Refer service to qualified personnel.
•
Do not open the cover while power is applied,
or within five minutes after removal of power.
• Potentially hazardous leakage current may
exist. Ensure the grounding is connected
before connecting the utility power.
P/N 48518 – Battery terminals can deliver
dangerous electrical shock. Service by
qualified service representatives only.
DANGER/ATTENTION
Risk of electrical shock. Do n ot touch u nin su lat ed
batt ery terminals. Batteries sh ould be serviced b y
qua lified service repre se ntative only. Miswiring of
batt ery could result in ele ctrcal sh ock a nd/or fire.
Risque de choc electrique . Le circuit des ba tteries
nest pa s e so led e secteur. Le s cosses des ba tteries
peu ven t prese nter une te nsion dange reu se part
rapport a la terre . Ve rifier avan t de to uch er.
P/N 49455 – UPS Batteries require an
-
nual preventative maintenance. Failure to
perform regular maintenance could result in
batteries exploding, or emitting gasses or
flame.
WARNING
This unit contains sealed lead acid batteries
.
Lack of preventative maintenance could result
in batteries exploding and emitting gasses and/or
flame. Annual preventative maintenance must be
performed by an authorized, trained technician.
P/N 49455 – Replace Fuse only
with one of same type and range.
Incorrect fuse size may result in
equipment damage.
WARNING
CRITICAL FUSE SIZING
Incorrect fu se replacem ent size
may result in fire or inadeq uate
equ ipm ent protection.
Re pla ce only with same t ype
and rating of fuse.
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......