57
1600XPi Series UPS Installation and Operation Manual – 60616-014
23.3 System Fault Messages
A Fault message is generated when either a fault condition occurs, or a warning condition occurs three times within ten
minutes. The table below shows the possible fault messages and what actions need be taken.
If the input voltage is normal when the fault occurs then the UPS will switch immediately to the bypass mode to continuously
feed power to the load.
If the fault condition occurs while the input power is abnormal and the UPS is in Bypass mode the UPS will shut down the
output to prevent load equipment damage.
When a Fault condition exists, the red LED on the UPS display panel will illuminate until the fault is cleared.
All faults are recorded. The fault status can cleared by cycling power (turn off, then turn on) after the problem has been
fixed.
Display
Recorded
Meaning
Action
BYPOH
Y
Bypass Overheat – Overheating
condition occurred.
Check unit for blocked or in-operable fan. Lower
ambient temperature if it is greater than 104 °F (40
°C). Bypass operation will also cease if overheat
condition is not corrected within 1 hr. of inverter
shutdown. Try restarting. If condition reoccurs plan
for total shutdown and call for service.
BYPOL
Y
Bypass Overload – UPS is over
-
loaded.
Shut down excess equipment to reduce load.
CHRGOV
Y
Charger Overvoltage – Charger
overvoltage condition occurred.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
CLMT
Y
Current Limit – Load on UPS out
-
put exceeds unit specifications.
Reduce load on UPS output.
DCIB
Y
DC Bus Imbalance – DC voltage
imbalance occurred.
Possible causes are UPS fault are connection of
half-wave rectifier load. Check load and try restart
-
ing. If condition persists,call Toshiba for service.
DCOC
Y
DC Bus Overcurrent – DC overcur
-
rent condition occurred.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
DCOV
Y
DC Bus Overvoltage – DC over
-
voltage condition occurred.
UPS is faulty, input wiring error, input overvoltage
or connection of a motor load. Try restarting. If con
-
dition persists call Toshiba for service.
DCUVBS
Y
DC Bus Undervoltage during
Boostup Mode – DC Bus under
-
voltage condition occurred.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
DCUVC
Y
DC Bus Undervoltage During
Charging Mode – DC Bus under
-
voltage condition occurred.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
DVCOH
Y
Device Overheat – Overheating
condition occurred.
Reduce equipment load to 100% or less and try
restarting.
EXTBC1
N
1.
BC1 Battery String 1, 2, or 3
Loose HCT Connection
2.
BC1 Over Voltage Fault
3.
BC1 Over Current Fault
•
Call Toshiba for Service.
•
Call Toshiba for Service
•
Call Toshiba for Service
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......