60
1600XPi Series UPS Installation and Operation Manual – 60616-014
Display
Recorded
Meaning
Action
OL110
N
Overload – UPS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Shut down excess equipment to reduce load.
REYEERR
N
Communication Error between
RemotEye and UPS.
Ensure RemotEye is connected to UPS. Call
Toshiba for service.
RS232ERR
N
Communication Error at Service
Port.
Call Toshiba for service.
REYEUER
N
Communication Error at LAN.
Call Toshiba for service.
VDCUVBT
N
DC Bus Undervoltage During Bat-
tery Test.
Call Toshiba for service.
VIOV
N
Input Overvoltage – Input voltage
exceeds UPS specifications.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
VIUV
N
Input Undervoltage – Input voltage
less than UPS specifications.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
23.5 System Mode Messages
A UPS Mode message is generated when the UPS changes operating mode. The following tables list the possible operat
-
ing modes for the UPS.
Display
Meaning
Backup
Backup – Power comes from other than input.
BattTest
Battery Test – Battery test in progress.
Bypass
Bypass – UPS is offline, power is being provided directly from UPS input.
On–Line
On-Line – Input converter and inverter are running (Double conversion mode).
Shutdown
Shutdown – No output, DC Bus is charged through Softstart Resistor.
Startup
Startup – UPS is starting up.
23.6 System Status Messages
A UPS Status message is generated when the UPS changes its status (from inverter to bypass mode, for example). The
table below shows the possible Status messages and their meaning.
Display
Meaning
Action
BYP
Bypass mode – Power is supplied by UPS input.
No action needed.
CHRGERR
Charger Error – Charger overvoltage error.
Call Toshiba for service.
DLYST
Delay Start – UPS is counting down prior to
startup.
No action needed.
EE1ST
EEPROM is loaded with default values.
No action needed.
EE2RAERR EEPROM to RAM loading Error.
Call Toshiba for service.
EEUPERR
EEPROM updating Error.
Call Toshiba for service.
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......