A1
1600XPi Series UPS Installation and Operation Manual – 60616-014
Appendix A: 1600XPi
Specifications
Standard Model: 3.6 – 10 kVA
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
General
Typeform
H3BG2L036C61T
H3BG2L060C61T
H3BG2L080C61T
H3BG2L100C61T
Certifications
UL 1778, CUL, RoHS Compliant
Input Characteristics
Input Voltage
1
Single-phase, 208/240 Vac, +10%
1,4
(to -30% at typical 70% load)
Input Frequency
45 – 65 Hz (auto-sensing)
Input Capacity
3.6 kVA
6 kVA
8.0 kVA
10 kVA
Input /(Max Input) Current @208V
17.9 (18.7) A
29.8 (31.1) A
38.9 (40.5) A
48.6 (50.2) A
Input/(Max. Input) Current @240V
15.5 (16.2) A
25.9 (27.0) A
33.7 (35.1) A
42.1 (43.5) A
Input Power Factor
0.98 Typical, 0.95 Minimum@ 100% Load
Current THD (linear load)
< 5% total harmonic distortion
Internal AC Input Breaker Rating
30 A/277 V
50 A/277 V
60 A/277 V
63 A/277 V
Battery Characteristics
Battery Type
Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged @ 0.7
power factor, 77 °F
8 min.
2
8 min.
2
7 min.
2
7 min.
2
Backup time, fully charged @ 0.85
power factor, 77 °F
7 min.
2
7 min.
2
7 min.
2
5 min.
2
Recharge Time
24 hr. (full), 12 hr. (90%) for internal batteries only
3
Battery Voltage (Nominal)
144 Vdc
216 Vdc
288 Vdc
Output Characteristics
Output Voltage
Single-phase, 240/208/120 V
Output Voltage Regulation
= ± 3%
Output Frequency
±0.5 Hz/1.0 Hz/1.5 Hz (factory or authorized service center selectable only)
AUTO/MAN Frequency
Factory or authorized service center selectable only
Voltage THD
< 3% for linear load; < 6% for non-linear load
Common-Mode Noise
< 0.5 Vrms
Rated Load Power Factor
1
0.85 (0.6 – 1.0) lagging
Efficiency (ac-dc-ac)
≥83%
>85%
Voltage Transient
< ±8% (Load of 0 – 100 %)
Voltage Transient Recovery
50 ms to within 2% of nominal
Rated Output Current (rms)
15 A
25 A
33.3 A
41.6 A
Inverter Overload Capacity
125% for 30 sec./150% for 10 sec.
Bypass Overload Capacity
125% for 10 min./1000% for 1 cycle
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2. Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
3. An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4. If Vin is below the minimum Vin window, the UPS goes to Battery Mode. If the UPS is in Fault and Vin is below the minimum
Vin window, the UPS goes to Bypass Mode
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......