B-20
1600XPi Series UPS Installation and Operation Manual – 60616-014
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
608
Current State of UPS
Current State
R
R
R
R
R
0: Shutdown [show Shutdown]
1: Initial Charge [show Shutdown]
2: Boostup [show Shutdown]
3: Normal (Online) [show Online]
4: Backup [show Backup]
5: Batttery
Test [show Battery
Test]
6: Bypass Normal [show Bypass]
7: Bypass Init [show Bypass]
8: Bypass Shutdown [show Bypass]
9: Startup [show Startup]
609
Operation
Mode T
ransition
State Requested
Requested State
R/W
R/W
R/W
R/W
R/W
1: Shutdown Request
2: Bypass Request
3: Online Request
4: Battery
Test Request
610
Operation
Mode T
ransition
Timer
Timed Operation
R/W
R/W
R/W
R/W
R/W
0 Sec
The timer upon whose expiration a mode transition
will be attempted by the system.
Range: 0 – 800
Units: Sec
611
EPO Contact State
EPO Status
R
R
R
R
R
Report of EPO input contact status.
0: Open
1: Closed
612
UPS Faults
Faults
R/W
R/W
R/W
R/W
R/W
Only accept zero to clear Fault bit map
613
UPS W
arnings
W
arnings
R
R
R
R/W
R/W
Only accept zero to clear W
arning bit map
614
UPS System Status
UPS Status(Comm)
R
R
R
R
R
LSW is attached at every data package. See the details of bit map UX3FN19 (T
oshiba
Communication Protocol (TUCP
2.0) for external
Reference.doc
615
Run / Stop mechanical switch
state
RunStop SW
Status
R
R
R
R
R
0: Stop
1: Run
617
Service Port Communication
Status
SPort Status
R
R
R
R
R
0
0: Unknown
1: Normal & OK
2: Idle – Off (Disable)
3: Error
618
Internal Communication Status
Inter Comm Status
R
R
R
R
R
0
0: Unknown
1: Normal & OK
2: Idle or Off (Disable)
3: Error
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......