B-21
1600XPi Series UPS Installation and Operation Manual – 60616-014
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
619
Security Level Control
(Enter Password)
Security Level
R/W
R/W
R/W
R/W
R/W
Reading will give the current security level
USER
for User Level
ADMIN
for
Administration Level
DIST
for Distrubutor Level
QCNSR
V
for Qc and Service Level
ENG
for Engineering Level
NOTE:
Three communication chanels have their
own security level variables
620
Manage
Admin Password
Manage Admin
PW
-
R/W
R/W
R/W
R/W
ADMIN
Change
Admin Password
621
Reset
Admin Password
Reset
Admin PW
R/W
R/W
R/W
R/W
R/W
0
0 = do nothing
1 = reset administration password
623
Bypass Enable*
En Bypass*
-
-
-
R/W
R/W
1: Enabled
DIP
Switch, EEPROM’
s Enable CVCF
, and this
value will decide the system’
s bypass availability
(Restart Required)
0: Disable
1: Enable
624
Enable
Transfer to Bypass
while in
Async mode
En
Asyn Byp
-
-
-
R/W
R/W
1: Enable
When Disabled, the UPS will not prevent transfers to
bypass mode during periods when the frequencies
are out of synch.
0: Disable
1: Enable
625
Enable CVCF*
En CVCF*
-
-
-
R/W
R/W
Constant V
oltage, Constant Frequency Mode
(Restart Required)
0: Disable
1: Enable
626
CVCF Output Frequency*
CVCF Frequency*
-
-
-
R/W
R/W
6000
500 or 600 Only
. Other values will default to 500
Systems.
(Restart Required)
Units: 0.1 Hz
634
System Date
UPS Date
R/W
R/W
R/W
R/W
R/W
Depends on which protocol is used.
SNMP
serial link and CAN communication –
1st Byte -> Day of W
eek (1 = Sunday
, 2 = Monday
,
…, 7 = Saturday)
2nd Byte -> Date
3rd Byte -> Month
4th Byte ->
Year (without 2000)
Hyper terminal -> “DOW MM/DD/YYYY”
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......