B-23
1600XPi Series UPS Installation and Operation Manual – 60616-014
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
649
Remote ‘Low Battery’
Delay
Timer
LB DContact Delay
R
R/W
R/W
R/W
R/W
0
Delay timer between actual event occurrence and dry contact closure to signal external devices of the
event.
Range: 0 – 800
Units: Sec
652
Enable Battery
Test on UPS
Startup*
En Batt
Test Sup*
R
R/W
R/W
R/W
R/W
0: Disabled
Forces a battery test when UPS starts after normal shutdown.
(Restart Required)
0: Disable
1: Enable
653
Enable Battery
Test*
En Batt
Test*
R
R/W
R/W
R/W
R/W
1: Enabled
(Restart Required)
0: Disable
1: Enable
654
Battery
Test Condition Status
Batt
Test Cond.
R
R
R
R
R
0
0 = Battery test prohibited because of battery test interval setup
1 = Battery test OK to perform
655
Battery
Test Frequency
Batt
Test Freq
R
R/W
R/W
R/W
R/W
2: Monthly
allow
0: only daily
1: only weekly
2: only monthly (Default for other values)
656
System T
emperature
Compensation
Sys.
Temp. Comp.
-
-
-
R/W
R/w
-5
Range: -20 – 20
Units: °C
657
Service Port Mode
Service Port Mode
-
-
-
R/W
R/W
1: Protocol Rqrd.
0:
Terminal mode (no handshake, no error check)
1:
Toshiba UPS Communication Protocol 2-0 mode
658
Enable Restart
(After Battery Shutdown)
En Restart
R
R/W
R/W
R/W
R/W
1: Enable
0: Disable
1: Enable
659
Restart Delay
(After Battery Shutdown)
Restart Delay
R
R/W
R/W
R/W
R/W
10 Sec
Range: 0 – 800
Units: Sec
660
Enable
Auto
Transfer
(Current Limit)
En
AutoXfer
R
R/W
R/W
R/W
R/W
1: Enabled
0 = keep inverter
,
1 = go to bypass and come back to inverter after
time delay CMD662
662
Auto ReT
ransfer Delay
(Current Limit)
AutoReXfer
Window
R
R/W
R/W
R/W
R/W
3 Sec
Time period to wait after current limit occurrence
before attempting tranfer back Online.
Range: 0 – 600
Units: Sec
663
Service Port Baud Rate
Settings*
Srv Port Baud*
R
R/W
R/W
R/W
R/W
3
no hardware control, no parity
, 1 stop bit, 8 bits of
data and baud rate are (Restart Required)
0: 9600
1: 19200
2: 38400
3: 57600
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......