1600XPi Series UPS Installation and Operation Manual – 60616-014
7 UPS Connections
7.1 Terminal Block - 208/240 V
IN
, 120/208/240 V
OUT
The following illustration is a detail view of the terminal block and wiring connections used for 208/240 volt units (see
“Appendix C: 1600XPi Dimensions and Weights” on page C1).
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or 11. Factory Setting is
208 Vac.
Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or 13.
Use the jumper
wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 3 –
EPO
and
Rmt Contacts
function – See Section 8.2
REMOTE1
208
EPO2
EPO1
REMOTE2
COM
240
G
X3
1
L2 (N*)
G
X1 X2
N (0V)
2
3
12
14
13
15
8
7
6
5
11
4
16
17
L1 (L*)
240V
208V
Jumper selection
See notes 1&2
208/240 V
in
INPUT
OUTPUT
Factory Installed N - G Jumper
1,2
Rmt Contacts
3
EPO
3
NO
NO
120 V
240 V
120 V
208 V
32 V
88 V
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......