13
1600XPi Series UPS Installation and Operation Manual – 60616-014
Input and Jumper wire/bus strip connection for:
208 Vin
– Using provided jumper, connect terminals 11 – 12.
REMOTE1
208
EPO2
EPO1
REMOTE2
COM
240
G
X3
1
L2
G
X1 X2
N
2
3
12
14
13
15
8
7
6
5
11
4
16
17
L1
Factory Installed N - G Jumper
Jumper
208 Vin
Rmt Contacts
EPO
NO
NO
120 V
240 V
120 V
208 V
32 V
88 V
240 Vin
– Using provided jumper, connect terminals 13 – 12.
REMOTE1
208
EPO2
EPO1
REMOTE2
COM
240
G
X3
1
L2
G
X1 X2
N
2
3
12
14
13
15
8
7
6
5
11
4
16
17
L1
Factory Installed N - G Jumper
Jumper
240 V
in
Rmt Contacts
EPO
NO
NO
120 V
240 V
120 V
208 V
32 V
88 V
Output Cabling for:
120 Vout
Connect load across Terminals 4 – 6 or 6 – 7.
208 Vout
Connect load across terminals 5 – 7.
240 Vout
Connect load across terminals 4 – 7.
120 V
120 V
G
X3
G
X1 X2
N
3
8
7
6
5
4
Factory Installed N - G Jumper
208 Vout
G
X3
G
X1 X2
N
3
8
7
6
5
4
Factory Installed N - G Jumper
240 Vout
G
X3
G
X1 X2
N
3
8
7
6
5
4
Factory Installed N - G Jumper
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......