1600XPi Series UPS Installation and Operation Manual – 60616-014
9.8 Battery Test
The 1600XPi allows the user to conduct automatic or manual battery tests as desired. The following steps detail the bat
-
tery test procedures.
Automatic Battery Test:
1.
The Automatic Battery Test Procedure is performed only if it is enabled during startup.
2.
Once the battery test is completed, Cmd
654 - Battery Test Condition Status
is set to
“Battery Test Prohibited”
. It
will be re-enabled once timer Cmd
655 - Battery Test Frequency
is reached.
Manual Battery Test:
The UPS must be in
Online
mode.
1.
Change the security setting to “ADMIN”.
2.
On the display, press the
Monitor
tab.
3.
On the display, press the
C&C
key.
4.
Use the Page (
<<
and
>>
) and Record (
<
and
>
) navigation keys to verify the following:
a. Cmd
652 - Battery Test Startup
must be set to
“Disable”
b. Cmd
653 - Enable Battery Test
set to
“Enable”
to allow the battery test to be performed.
c. Cmd
655 - Battery Test Frequency
should be set to
“0”
(Daily Test)
d. Cmd
654 - Battery Test Condition Status
should read
“Enable - Battery Test OK
to perform”
NOTE: If Cmd
654
is
“Disable”
, the user will have to power down and restart the unit to perform the battery
test.
e. Navigate to Cmd
609 - Requested State
and press the
“BattTest”
button on the display.
•
If the test passes, the display returns to the Monitor screen.
•
If the test fails, the display returns to the Monitor screen and displays BTSTFL in the warning section at the bot
-
tom left of the display, and the “Warning” LED blinks until the fault is cleared.
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......