23
1600XPi Series UPS Installation and Operation Manual – 60616-014
TABLE 10.1: INITIAL BATTERY PARAMETER SETTINGS - MATCHING BATTERY CABINETS
Parameter
Description
UPS
Size
UPS
Only
UPS +
1 BC
1
UPS +
2 BC
1
511
Internal Battery Capacity in A-hr
All
9
9
9
512
# Internal Batteries in Series String
3.6 kVA
12
12
12
5.2–6 kVA
18
18
18
8–22 kVA
24
24
24
513
# Internal Battery Strings in Parallel
3.6–10 kVA
1
1
1
14–22 kVA
2
2
2
522
Enable Ext. Battery Cabinet BC1
3.6–22 kVA
Disable
Enable
Enable
523
Enable Ext. Battery Cabinet BC2
3.6–22 kVA
Disable
Disable
Enable
524
External Batt. Cabinet Status
All
0
1
1
525
# External Batt. Packs in Series String
(H3B-BC-0370)
3.6 kVA
0
12
12
(H3B-BC-0650)
6 kVA
0
18
18
(H3B-BC-1825)
8–22 kVA
0
24
24
526
# External Batt. Strings in Parallel
(H3B-BC-0370)
3.6 kVA
0
3
6
(H3B-BC-0650)
5.2–6 kVA
0
2
4
(H3B-BC-1825)
8–22 kVA
0
3
6
527
External Battery Capacity in A-hr
All
0
9
9
1 These settings apply to 1600XPi matching battery cabinets.
TABLE 10.2: INITIAL BATTERY PARAMETER SETTINGS - NON-MATCHING BATTERY CABINETS
Parameter
Description
UPS
Size
UPS +
1 BC
1
511
Internal Battery Capacity in A-hr
All
9
512
# Internal Batt. Packs in Series String
3.6 kVA
0
5.2–6 kVA
0
8–22 kVA
0
513
# Internal Batt. Strings in Parallel
3.6–22 kVA
1
522
Enable Ext. Battery Cabinet BC1
All
Disable
523
Enable Ext. Battery Cabinet BC2
All
Disable
524
External Batt. Cabinet Status
All
1
525
# External Batteries in Series String
3.6 kVA
12
5.2–6 kVA
18
8–22 kVA
24
526
# External Batt. Strings in Parallel
3.6–22 kVA
See Note 3
527
External Battery Capacity in A-hr
All
9
1 Battery runtimes on the UPS display will
not
be accurate when using a non-Toshiba external battery cabinet.
2. Internal battery trays MUST be removed before connecting UPS to non-matching battery cabinet.
3. Set parameter 526 as (External Battery Capacity – 9 Amp Hr) / 9 Amp Hr.
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......