61
1600XPi Series UPS Installation and Operation Manual – 60616-014
Display
Meaning
Action
EPO
EPO circuit is active.
Reset EPO switch to start.
FIERRST
Frequency Input Error Start – Input frequency
could not be detected and UPS starts up with
default EEPROM setup.
Ensure correct input frequency is
selected in UPS settings.
FLT
A fault has occurred.
See Fault records.
FWUPERR
Firmware Update Error.
Call Toshiba for service.
INIT
Initialization – UPS is inatilizing.
No action needed.
INV
Inverter mode.
Inverter is running (it can be On-
Line, Battery Test, or Backup)
LANSD
UPS goes to Shutdown triggered from customer
supplied LAN SD circuit.
Deactivate LAN shutdown signal to
reset.
LB
Low Battery – The battery level has dropped low
(about 90% or less) during operation. Continued
operation in this mode will deplete battery and
cause output shut down.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
PFAIL
Input power failure.
No action needed.
RMTSD
Remote shutdown occurred.
Disconnect LAN signal to reset.
RO2EEERR ROM to EE Loading Error.
Call Toshiba for service.
SYNC
Synchronous mode.
Input and output are synchronized.
TIMEDSD
UPS is counting down prior to shutdown.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
WRN
A warning has occurred.
See Warning record.
24 Preventive Maintenance/Parts Replacement
24.1 Preventive Maintenance
Toshiba 1600XPi Series of uninterruptible power systems have been designed to provide years of trouble-free operation
requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents,
clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum
cleaner to periodically remove dust accumulations around and from the unit.
CAUTION
Only a qualified Toshiba representative should be allowed to perform any
routine maintenance or service on this equipment other than those preventive
maintenance details which are described directly above this caution.
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......