A3
1600XPi Series UPS Installation and Operation Manual – 60616-014
Unit (Capacity)
3.6kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
10 kVA (8.5 kW)
1
Remote Contacts
Standard (INV, BYP, BATT, LB, AC, FLT)
RS232 ASCII Interface
Toshiba UPS Communication Protocol 2.0
RemotEye 4
(Standard with XPi)
Remote communications package (HTTP/HTTPS, SNMP, Modbus TCP/RTU, BACnet IP/MSTP)
via RJ-45 or RS-485
Mechanical Design
Topology
Unit enclosure is made from sheet metal meeting NEMA1 and UL Type 1
Size (HxWxD) (max)
22.1x 10 x 34 in.
(561 x 254 x 864
mm)
27.5 x 10 x 34 in.
(699 x 254 x 864
mm)
28.4x 13 x 34.9 in.
(721 x 330 x 886
mm)
28.4x 13 x 34.9 in.
(721 x 330 x 886 mm)
Paint System
Powder coating
Fan Panel
2
Panel mounted on back of UPS to allow for easy replacement of fans
Battery System
Battery Replacement
Slide out battery packs accessible from front of UPS. Factory or authorized service center
serviceable only.
Battery Packs
Designed for battery acid leakage containment with six (6) batteries per pack
Battery Pack Size
(HxWxD) max.
5.0 x 7.3 x 19.0 in.
(127 x 185 x 483 mm)
Battery Pack Quantity
2
3
4
Battery Type
Lead Acid 9AH/12V (FR)
Toshiba’s Part Number for Battery
Pack
51896-FS
60995-FS
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when the input voltage
is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
Remove all sources of main AC power and wait five minutes before replacing fans.
STANDARD MODELS: 3.6 – 10 KVA (CONT’D)
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......