A5
1600XPi Series UPS Installation and Operation Manual – 60616-014
STANDARD MODELS: 14 – 22 KVA (CONT’D)
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2. At 6600 ft (2000 m) above sea level, output capacity should be derated by 3% per additional 1000 feet elevation.
3. Subject to update without notice.
4. Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.
Capacity
14 kVA (11.9 kW)
1
18 kVA (15.3 kW)
1
22 kVA (18.7 kW)
1, 5
Bypass Overload Capacity
125%-10 min./1000%-1 cycle
Crest Factor
3.0
Environment
Operating Temperature 59 – 77 °F (15
– 25 °C) Recommended
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
Storage Temperature
-4 – 104 °F (-20 – 40 °C)
Installation Area
To be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
Operating Humidity
30 – 90% (no condensation)
Altitude
< 6600 ft. (2000 m) above sea level
2
Acoustical Noise
50 dB (A) maximum @ 1 meter from front panel
Heat Generation (Typical)
6610 BTU/Hr
3
8499 BTU/Hr
3
10,387 BTU/Hr
3
Operation Diagnosis
Battery Check
Performed on start up, by schedule, on-demand (user configurable)
Input OV Protection
Standard
Battery Lifetime
UPS calculates
battery replacement time based upon
battery ambient temperature (LCD display, LED and beeps)
Internal Temperature
UPS gives indication of internal temperature, alarm when high temp
Event Data Storage Registers
32 – Operation, 32 – Backup, 32
–
Warnings, 32 – Faults, 32
–
Test,
32
–
System
Applications
Switches
Generator compatible
Bypass Switch
Bypass Disable
Static switch <1/4 cycle (50Hz: 5 ms/60Hz: 4.16 ms)
Automatic Retransfer
Factory or authorized service center selectable only
Interface/Communications
Real Time clock
Real Time
Clock with backup Lithium Ion Battery
Schedule Operation
Schedule ON/OFF operation of UPS using optional RemotEye III communication software
Autostart
Automatic UPS Startup when AC is applied – Option can be enabled or disabled at user’s
discretion
Remote ON/OFF
Standard – External terminal
LED Display
3 LED’s indicating On-Line/Fault, Warning, and A/C Input
Operator Interface
Interactive Touchscreen
Buzzer Volume
Standard (Fixed Volume)
Power Connections
Standard – Hard wire
Emergency Power Off
Standard – Terminal contacts only
Summary of Contents for 1600XPi SERIES
Page 2: ......
Page 6: ...This Page Left Intentionally Blank ...
Page 10: ...This Page Left Intentionally Blank ...
Page 78: ...This Page Left Intentionally Blank ...
Page 88: ...This Page Left Intentionally Blank ...
Page 118: ...This Page Left Intentionally Blank ...
Page 120: ...C2 1600XPi Series UPS Installation and Operation Manual 60616 014 5 2 6 kVA Dimensions ...
Page 121: ...C3 1600XPi Series UPS Installation and Operation Manual 60616 014 8 10 kVA Dimensions ...
Page 122: ...C4 1600XPi Series UPS Installation and Operation Manual 60616 014 14 22 kVA Dimensions ...
Page 130: ......
Page 138: ...This Page Left Intentionally Blank ...
Page 139: ......