*UPS1800epXT070225*
CAPACITY
2400 VA
INPUT
Voltage
Single-Phase 208/240 Vac (3 Wire Input/L-L,G)
Voltage Range
144 V to 264 V (+10% to -40%)
Frequency
50/60 Hz Auto-Sensing
Synchronization Window
± 3 Hz
Power Factor
Greater than 0.95
OUTPUT
Voltage
120/208/240 Vac (3 Wire Input/L-L,G)
Capacity (VA/W)
2400 VA*/1680 W*
Voltage Regulation
± 3%
Voltage Distortion
Less than 5% THD at Full Non-Linear Load. Less than 3% THD at Full Linear Load.
Step Load
± 9% Max. from 100% to 0% or from 0% to 100% Linear Load
Rated Current at 240 V
9.6 A
Overload Capacity
125% for 1 Minute; 150% for 30 Seconds
Crest Factor
2.5 at Full Load
Frequency
50/60 Hz Auto-Sensing (± 0.5 Hz)
Wave Form
Sine Wave, Zero Transfer Time
Load Power Factor
0.7
Efficiency AC to DC to AC
80%
BATTERY
DC Voltage
48 V
Backup Time (Full Load)
7 Minutes
Battery Type
Enersys NPX-35FR Lead Acid 9 Ah/12 V
Number of Batteries
Two (2) Strings in Parallel, Four (4) Batteries per String
PHYSICAL
Interface
RS-232, Dry Contact, External Battery Connectors
Line Cord and Receptacles
Hardwired (With Optional Line Cord & Receptacle Panels)
Dimensions
254 W x 686 D x 597 H mm (10 W x 27 D x 23.5 H in.)
Weight
77 kg (170 lbs.)
OPTION
Network Interface Card
RemotEye
®
II Part #: RMTI-INT-R4
Environmental Monitoring
Device
Part #: RMTI-EMD-HT
ENVIRONMENT
Operating Ambient Temperature
0 to 40° C (32 to 104° F)
Humidity
30% to 90%, Non-Condensing
Audible Noise
Less than 50 dB Normal and Battery Modes
Altitude
1000 m (3000 ft) Above Sea Level
CONFORMANCE
Regulatory Approvals
UL1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001, ISO 140001, NEMA/PE1-
1993
Warranty
Three (3) Years on Electronics
Two (2) Years Full Replacement on Batteries (See Toshiba Warranty Policy for Full Details)
*208/240 Transformer Models Result in 5% Derating
CONV
208/240 V
50/60 Hz
Input
INV
Internal Batteries
DC CONVERTER
UPS Cabinet
208/240 V MODEL
STATIC BYPASS
120/208/240 V,
50/60 Hz
Output