1800 Series User Manual
29
W
arning
Description and Resolution
The batteries have less than 30%
power remaining.
The warning will
continue until either the batteries become completely exhausted or AC input power is restored.
An output current limit warning is typically a sign of misapplication. The load may not be appropri
-
ate for UPS support. For further explanation contact your
Toshiba
UPS service representative at 1-
877-867-8773 (outside the U.S. call 713-466-0277).
The temperature of the UPS operating environment is too high. Causes of this condition include allowing the room
temperature to exceed 104°F (40°C), a
blocked vent, or direct sunlight on the unit.
The unit will transfer to bypass
mode until the temperature is reduced. If temperature is not reduced after an allowable time, the unit will shut down.
Alarm State
Alarm will sound for 1-second at 5- second intervals.
Alarm will sound for 1/2- sec
-
ond at 1-second intervals.
Alarm will sound for 1-second at 15- second intervals.
LED State
W
arning/Fault Flash
Backup
Flash
W
arning/Fault Flash
80%
Flash
W
arning/Fault Flash
100%
Flash
Display State
W
arning
Low Battery
Current Limit (Over Current)
Ambient Over Heat
Summary of Contents for 1800 SERIES