background image

EN

ES

FR

IT

DE

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

7

 

A

90

CAUTION

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

 • 

Projection margin in 

fl

 aring : A (Unit : mm)

Rigid (clutch type)

Imperial (wing nut type)

Outer dia. of copper pipe

R410A

6.35 mm

1.5 to 2.0

12.70 mm

2.0 to 2.5

Align the centers of the connecting pipes and tighten the 

fl

 are nut as far as 

possible with your 

fi

 ngers. Then tighten the nut with a spanner and torque 

wrench as shown in the 

fi

 gure.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

6.35 mm

14 to 18 (1.4 to 1.8 kgf·m)

12.70 mm

50 to 62 (5.0 to 6.2 kgf·m)

Evacuating

After the piping has been connected to the indoor unit, you can perform 
vacuuming together at once.

VACUUMING

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

Outer dia.

of copper pipe

R410A tool used

Conventional tool 

used

6.35 mm

0 to 0.5

1.0 to 1.5

12.70 mm

0 to 0.5

1.0 to 1.5

• 

Tightening torque for connection of 

fl

 are pipe

 

The pressure of R410A is higher than 
R22. (Approx. 1.6 times.) Therefore 
securely tighten the 

fl

 are pipes which 

connect the outdoor unit and the 
indoor unit with the speci

fi

 ed tightening 

torque using a torque wrench. If any 

fl

 are pipe is incorrectly connected, it 

may cause not only a gas leakage but 
also trouble in the refrigeration cycle.

     Flaring

1.  Connect the charge hose from the manifold valve to the service port of 

the packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4.  Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 20 meters. (15 minutes for 20 
meters) (assuming a pump capacity of 27 liters per minute) Then con

fi

 rm 

that the compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

fl

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

•  Open the valve stem until it touches the stopper. Once it is in contact with 

the stopper, refrain from applying any more force than is necessary.

•  Securely tighten the valve stem cap with torque in the following table:

     Packed valve handling precautions

Gas side
(dia. 12.70 mm)

50 to 62 N·m
(5.0 to 6.2 kgf·m)

Liquid side
(dia. 6.35 mm)

14 to 18 N·m
(1.4 to 1.8 kgf·m)

Service port

14 to 18 N·m
(1.4 to 1.8 kgf·m)

• 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.

CAUTION

Wiring Connection

1.  Remove the valve cover, the electric parts cover and the cord clamp from 

the outdoor unit.

2.  Connect the connecting cable to the terminal as identi

fi

 ed by the 

matching numbers on the terminal block of indoor and outdoor unit.

3.  Insert the power cord and the connecting cable fully into the terminal 

block and secure it tightly with screws.

4.  Use vinyl tape, etc. to insulate the cords which are not going to be used. 

Locate them so that they do not touch any electrical or metal parts.

5.  Secure the power cord and the connecting cable with the cord clamp.
6.  Attach the electric parts cover and the valve cover on the outdoor unit.

Electrical Work

1.  The supply voltage must be the same as the rated voltage of the air 

conditioner.

2.  Prepare the power source for exclusive use with the air conditioner.

 

NOTE

•  Wire type : H07RN-F or 60245 IEC66 (1.5 mm

2

 or more)

Be sure to use a vacuum pump with counter-

fl

 ow prevention function so 

that inside oil of the pump does not 

fl

 ow backward into pipes of the air 

conditioner when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use 
R410A, refrigeration cycle trouble may happen.)

     Using a vacuum pump

Obliquity

Roughness

Warp

Half uniont

Flare nut

Externally
threaded side

Internally
threaded side

Pipe

Die

Flare at
indoor unit side

Flare at
outdoor unit side

Hexagon wrench
is required.

4 mm

Use a wrench to secure.

Use a torque wrench to tighten.

1110651154-EN.indd   7

1110651154-EN.indd   7

2/15/10   9:39:41 AM

2/15/10   9:39:41 AM

Summary of Contents for 22SAV

Page 1: ...r unit RAS 18 22SKV R Series Outdoor unit RAS 18 22SAV Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651154 Cover 1110651154 indd 1 Cover 1110651154 indd 1 1 22 10 11 14 26 AM 1 22 10 11 14 26 AM ...

Page 2: ...Installation 5 n Indoor Unit Fixing 6 n Drainage 6 OUTDOOR UNIT 6 n Installation Place 6 n Precautions about Installation in Regions with Snowfall and Cold Temperatures 6 n Refrigerant Piping Connection 7 n Evacuating 7 n Wiring Connection 7 n Electrical Work 7 OTHERS 8 n Gas Leak Test 8 n Remote Control A B Selection 8 n Test Operation 8 n Auto Restart Setting 8 Cover 1110651154 indd 2 Cover 1110...

Page 3: ...ing in damage to the unit or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock If you detect any damage do not install the unit Contact your supplying dealer immediately New refrigerant air conditioner installation CAUTION THIS AIR CONDI...

Page 4: ...use electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage causing water damage to furniture Tighten the flare nut with a torque wrench using the prescribed method Do not apply excess torque Otherwise the nut may crack after a long period o...

Page 5: ...rain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 8 mm thick heat resisting polyethylene foam 1 Batteries Pan head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddl...

Page 6: ...he pipe hole dia 65 mm at a slight downward slant to the outdoor side A place which provides the spaces around the indoor unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor uni...

Page 7: ...pipe make sure to use a spring bender so as not to crush the pipe Bend the connecting pipe within a radius of 30 mm To connect the pipe after installation of the unit figure How to install the air inlet grille on the indoor unit When attaching the air inlet grille perform the same process as for removal but in reverse order Wiring Connection Wiring of the connecting cable can be carried out withou...

Page 8: ...cause any problems CAUTION 1 Install the outdoor unit in a location where there are no obstructions near its air intake or air outlet 2 When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a high story of a building secure the normal fan operation using a duct or a wind shield 3 Especially in windy areas install the unit to prevent the admiss...

Page 9: ...uid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Handle Hi Keep full closed Manifold valve Pressure gauge Compound pressure gauge Handle Lo Charge hose For R410A only Connecting pipe 101 kPa 76 cmHg Open the valve stem until it touches the stopper Once it is in contact with th...

Page 10: ...ns for the gas leak with a gas leak detector or soap water This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure 1 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beep sound and OPERATION lamp blink 5 time sec for 5 seconds 2 Press and hold the RESET button on the indoor uni...

Page 11: ...Cover back 1110651154 indd 1 Cover back 1110651154 indd 1 1 22 10 11 15 21 AM 1 22 10 11 15 21 AM ...

Page 12: ...Cover back 1110651154 indd 2 Cover back 1110651154 indd 2 1 22 10 11 15 22 AM 1 22 10 11 15 22 AM ...

Reviews: