background image

6

Toshiba 1110651160 (EN)

A

90

Refrigerant Piping Connection

Tightening connection

Align the centers of the connecting pipes and tighten the fl are nut as far as 

possible with your fi ngers. Then tighten the nut with a spanner and torque 

wrench as shown in the fi gure.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

6.35 mm

16 to 18 (1.6 to 1.8 kgf·m)

1.70 mm

50 to 6 (5.0 to 6. kgf·m)

15.88 mm

65 to 80 (6.5 to 8.0 kgf·m)

Evacuating

 

Tightening torque of flare pipe connections

Flaring

1. Cut the pipe with a pipe cutter.

Obliquity

Roughness

Warp

Half union

Flare nut

Pipe

Die

Flare at

indoor unit side

Flare at

outdoor unit side

Use a wrench to secure.

Use a torque wrench to tighten.

Outer dia.

of copper pipe

A

Rigid

Imperial

6.35

1.0 to 1.5

1.5 to .0

1.70

1.0 to 1.5

.0 to .5

15.88

1.0 to 1.5

.0 to .5

CAUTION

Do not apply excess torque. Otherwise, the nut may crack depending on 

the conditions.

Internally

threaded side

Externally

threaded side

CAUTION

 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

(1) Take away dust and moisture (inside of the connecting pipes).

() Tighten the connections (between pipes and unit).

(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.

(4) Check gas leak (connected points).

(5) Be sure to fully open the packed valves before operation.

After the piping has been connected to the indoor unit, you can perform the 

air purge together at once.

Using a vacuum pump

Be sure to use a vacuum pump with counter-fl ow prevention function so 

that inside oil of the pump does not fl ow backward into pipes of the air 

conditioner when the pump stops.

 

A

1. Connect the charge hose from the manifold valve to the service port of 

the packed valve at gas side.

. Connect the charge hose to the port of the vacuum pump.

3. Open fully the low pressure side handle of the gauge manifold valve.

4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 0 meters. (15 minutes for 0 

meters) (assuming a pump capacity of 7 liters per minute) Then confi rm 

that the compound pressure gauge reading is –101 kPa (–76 cmHg).

5. Close the low pressure side valve handle of the gauge manifold valve.

6. Open fully the valve stem of the packed valves (both gas and liquid 

sides).

7. Remove the charging hose from the service port.

8. Securely tighten the caps on the packed valves.

Packed valve at liquid side

Vacuum

pump

Handle Lo

–101 kPa

(–76 cmHg)

Packed valve handling precautions

 Open the valve stem until it touches the stopper. Once it is in contact with 

the stopper, refrain from applying any more force than is necessary.

 Securely tighten the valve stem cap with torque in the following table:

Wiring Connection

1. Remove the valve cover, the electric parts cover and the cord clamp from 

the outdoor unit.

. Connect the connecting cable to the terminal as identifi ed by the matching 

numbers on the terminal block of indoor and outdoor unit.

3. Insert the power cord and the connecting cable carefully into the terminal 

block and secure it tightly with screws.

4. Use vinyl tape, etc. to insulate the cords which are not to be used. 

    Locate them so that they do not touch any electrical or metal parts.

5. Secure the power cord and the connecting cable with the cord clamp.

6. Attach the electric parts cover and the valve cover on the outdoor unit.

Electrical Work

1. The supply voltage must be the same as the rated voltage of the air 

conditioner.

. Prepare the power source for exclusive use with the air conditioner.

TO CHARGE REFRIGERANT

Refrigerant

18 Class

24 Class

Non refrigerant charging

Less than 15 m

Less than 15 m

Refrigerant charging

15 – 0 m (0g/m)

15 – 5 m (30g/m)

Hexagon wrench

is required.

Pipe side

Tightening torque

A

Gas side

(

15.88 mm)

65 to 80 N·m

(6.5 to 8.0 kgf·m)

5 mm

Gas side

(

1.70 mm)

50 to 6 N·m

(5.0 to 6. kgf·m)

4 mm

Liquid side

(

6.35 mm)

16 to 18 N·m

(1.6 to 1.8 kgf·m)

Same as

gas side

Service port

9 to 10 N·m

(0.9 to 1.0 kgf·m)

Vacuum pump adapter for

counter-fl ow prevention

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 

vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see 

the manual of the vacuum pump.

Service port (Valve core (Setting pin))

Charge hose

Charge hose

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Hi

(Keep full closed)

Connecting pipe

Packed valve at gas side

. Insert a fl are nut into the pipe and fl are the pipe.
 

 

Projection margin in flaring : A (Unit : mm)

Summary of Contents for 24S Series

Page 1: ...1 Toshiba 1110651160 COVER_F ENGLISH Indoor unit RAS 18 24SK Series Outdoor unit RAS 18 24S Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651160 ...

Page 2: ...tion Plate 3 nWiring Connection 4 nPiping and Drain Hose Installation 4 nIndoor Unit Fixing 5 nDrainage 5 EN OUTDOOR UNIT 5 nInstallation Place 5 nPrecautions about Installation in Regions with Snowfall and Cold Temperatures 5 nRefrigerant Piping Connection 6 nEvacuating 6 nWiring Connection 6 nElectrical Work 6 OTHERS 7 nGas Leak Test 7 nRemote Control A B Selection 7 nTest Operation 8 nAuto Rest...

Page 3: ...WAY MORE THAN M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTING...

Page 4: ...er operation Do not allow the drain hose to get slack Make sure to run the drain hose sloped downward Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Left Bottom right Rear left Bottom left Insulate the refrigerant pipes separately with insulation not together 8 mm thick heat resisting pol...

Page 5: ...nything on the top of the indoor unit The center of the pipe hole is above the arrow Pipe hole In case of block brick concrete or similar type walls make 5 mm dia holes in the wall Insert clip anchors for appropriate mounting screws 7 Indoor unit Side view Top view Indoor unit Remote control Remote control Reception range R e c e p t i o n r a n g e Installation plate Keep horizontal direction 5 m...

Page 6: ... the connecting pipe so that it is laid within 43 mm above the wall surface If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend the connecting pipe within a radius of 30 mm To connect the pipe after installation of the unit figure Inse...

Page 7: ...ion drain hose insulate the connecting part of extension drain hose with shield pipe NOTE The hole should be made at a slight downward slant on the outdoor side CAUTION Arrange the drain pipe for proper drainage from the unit Improper drainage can result in dew dropping 1 Installation plate Information The lower part of indoor unit may float due to the condition of piping and you cannot fix it to t...

Page 8: ...handle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Packed valve at liquid side Vacuum pump Handle Lo 101 kPa 76 cmHg Packed valve handling precautions Open the valve stem until it touches the stopper Once it is in contact with the stopper refr...

Page 9: ... 3 2 Terminal block Cord clamp Earth line Terminal screw Cord clamp Screw Power supply cord Connecting cable For 18 Class For 24 Class Earth line Stripping length of the connecting cable CAUTION Wrong wiring connection may cause some electrical parts burn out Be sure to comply with local rule on running the wire from indoor unit to outdoor unit size of wire and wiring method etc Every wire must be...

Page 10: ...3 beep sound but OPERATION lamp does not blink In case of ON timer or OFF timer are set AUTO RESTART OPERATION does not activate This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure To switch the TEST RUN COOL mode press RESET button for 10 seconds The beeper will make a short beep RESET Hi POWER FILTER PAP TIMER...

Reviews: