4200FA Installation and Operation Manual
35
5.3
4200FA 15/25 kVA w/Internal Transformer
Model Number
C42#3*150#AMXN, -S
C42#3*250#AMXN, -S
Input
# =
(B: 208; H: 220; C: 240; N: 380–415
∆
-wye; P: 380–415 wye; D: 480;
M: 600) VAC
Output
*=
(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600) VAC
Rated Output Capacity
15 kVA
25 kVA
External Dimensions
W x D x H (cm)
w/ casters: 20.0” x 36.3” x 59.7”(50.8 cm x 92.2 cm x 151.6 cm)
w/o casters: 20.0” x 36.3” x 60.0”(50.8 cm x 92.2 cm x 152.4 cm)
Input
Rated Voltage
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
Voltage Variation
4,5
+10% to -15%; (-10% to -15%)
4
, (-15 to -30%)
5
Rated Frequency
50/60 Hz
Input Cables Required
3 phase ; 3 Wire + GND
Dual Input Option Cables required
3 phase ; 4 Wire + GND
Power Factor
1
Greater than 0.98 when in inverter mode
1
Required Input kVA
16 kVA
26 kVA
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times the rated current under synchronous operation
Current Limit
115% maximum
Harmonic Currents
1
Less than 8.5%
1
Less than 5.5%
1
Battery
DC Nominal (Voltage Range)
288 VDC (216 – 332 VDC)
Float Charge (Regulation)
324.0 VDC (
±
2%)
Ripple Voltage
0.5 V R.M.S.
Rated Back-up Time
2
Refer to Battery System Manual
2
Rated Charge Current
10.0 Amps
Output
Rated Voltage
(Determined by Output Transformer internal to the unit)
Rated Current
VA / Nominal Output Voltage / 1.73
Rated Power Factor
0.8 lagging
Output Cables Required
3 phase ; 4 Wire + GND
Voltage Regulation (phase-phase)
±
5% (0 – 100% balanced load);
±
6% (0 – 100% unbalanced load)
Voltage Adjustment Range
±
5V Manually from key pad
Phase Displacement
±
2
°
(0 –100% balanced load);
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
±
0.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
Voltage Transients
(Recovery time: 50 ms)
±
5% (100% load step change);
±
3% (loss or return of input voltage);
±
8% (transfer from bypass to inverter)
Inverter Overload Capacity
125% for 90 sec; 150% for 30 sec
Bypass Overload Capacity
1000% for 10ms; 125% for 10 min.
Crest Factor
2.5 – 3.0 within the kW range
Neutral Line Conductor
1.73 times line rating
Harmonic Voltage Distortion
1.5% max (linear load)
Inrush Current protection
Automatic Transfer to bypass, then retransfer to inverter
Environment
Efficiency (Typical)
AC/DC/AC – See Table 5.10,
DC/AC: 82%
AC/DC/AC – See Table 5.10,
DC/AC: 83%
Heat loss to be removed
See Table 5.10
See Table 5.10
Audible Noise
60dB (A) at 1 meter from the front of the unit
Operating Temperature
32 – 104
°
F (0 – 40
°
C); optimal temperature is 77
°
F (25
°
C)
Operating Humidity
30 – 90% RH (non condensing)
Altitude
3
Less than 2000 meters
3
1
–
Specified at rated conditions under balanced linear loads.
2
–
Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. An initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
3
–
At 6600 ft. (2000 m) above sea level, output capacity should be derated by 3% (Consult factory for higher elevations).
4 – Prolonged operation at this level requires derating of the maximum Operating Temperature to 90
°
F ( 32
°
C).
5 – SHORT TERM operation only (e.g. Brownouts). Operation at this level requires derating the maximum Operating Temperature to 95
°
F ( 35
°
C).
Summary of Contents for 4200FA CT
Page 2: ...4200FA Installation and Operation Manual ...
Page 4: ...4200FA Installation and Operation Manual ...
Page 10: ...iv 4200FA Installation and Operation Manual This Page Intentionally Left Blank ...
Page 14: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 85: ...4200FA Installation and Operation Manual 75 APPENDIX A Seismic Anchorages ...
Page 86: ...76 4200FA Installation and Operation Manual ...
Page 87: ...4200FA Installation and Operation Manual 77 ...
Page 88: ...78 4200FA Installation and Operation Manual ...
Page 96: ......
Page 97: ......