4200FA Installation and Operation Manual
81
Installation Planning Guide for 15-80kVA UPS
Standard System: 208v (Isolation Xfmr.) Input, 208/120V Output
For Maximum cable sizes, see Note 7.
General Mechanical Information
UPS kVA/ kW Rating
Dimensions
(W x D x H)
Weight
Lbs.
Approximate Full-Load
Heat Loss
Inches
kBTU’s / Hr
15 kVA/12 kW
20 x 36.3 x 59.7
783
6.4
25 kVA/ 20 kW
20 x 36.3 x 59.7
793
9.1
30 kVA/ 24 kW
20 x 36.3 x 59.7
798
12.8
50 kVA/ 40 kW
35.5 x 38.3 x 59.3
1,581
21.3
Primary AC Input (208V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External Feeder
Breaker
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
>0.97
47
60 A
(1) x 6
380
25
>0.97
72
90 A
(1) x 3
380
30
>0.97
87
110 A
(1) x 1
380
50
>0.97
140
175 A
(1) x 2/0
380
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External Feeder
Breaker
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
42
60 A
(1) x 6 / (1) x 4
380
25
67
90 A
(1) x 3 / (1) x 1
380
30
81
110 A
(1) x 1/ (1) x 1
380
50
138
175 A
(1) x 3/0 / (1) x 250
380
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
15
64
70 A
(1) x 4
70
25
24
105
110 A
(1) x 1
70
30
29
126
150 A
(1) x 1
70
50
47
204
225 A
(1) x 250
70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External Feeder
Breaker
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
0.8
42
60 A
(1) x 6 / (1) x 4
380
25
0.8
69
90 A
(1) x 3 / (1) x 1
380
30
0.8
83
110 A
(1) x 2 (1) x 3/0
380
50
0.8
139
175 A
(1) x 2/0 / (1) x 250
380
Summary of Contents for 4200FA CT
Page 2: ...4200FA Installation and Operation Manual ...
Page 4: ...4200FA Installation and Operation Manual ...
Page 10: ...iv 4200FA Installation and Operation Manual This Page Intentionally Left Blank ...
Page 14: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 85: ...4200FA Installation and Operation Manual 75 APPENDIX A Seismic Anchorages ...
Page 86: ...76 4200FA Installation and Operation Manual ...
Page 87: ...4200FA Installation and Operation Manual 77 ...
Page 88: ...78 4200FA Installation and Operation Manual ...
Page 96: ......