4200

FA 

XT

 

15/25/30/50/80 kVA UPS

UPS Cabinet

AC Output

208-600 V

3 Ph/4 W,

50/60 Hz

Static Bypass Switch

External Battery Cabinet(s) or Rack(s) with DC Breaker

AC Input

208-600 V,

3 Ph/3 W,

50/60 Hz

Maintenance Bypass Switch

Converter

DC Chopper/

Charger

SYNC

Inverter

Isolation

Transformer

D

Y

Make-Before-Break

Output

Transformer

Y Y

High

Freq.

Filter

High

Freq.

Filter

Contactor

MCCB

Contactor

*UPS4200FAXT061118*

* Not available on 80 kVA

Model Number

T42X3X150XAMXN

T42X3X250XAMXN

T42X3X300XAMXN

T42X3X500XAMXN

T42X3X800XAXXN

Capacity

kVA/kW

15/12

25/20

30/24

50/40

80/64

Topology

True On-line, Double Conversion, IGBT PWM, with Active Input Power Factor Correction

Input

Voltage

208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 3 w + Gnd

Voltage Range

+10% to -30%; +20% to -30% Online (Without Utilizing Battery)

Power Factor

Greater than 0.99

Current THD

Less than 3%

Frequency

50/60 Hz  (range 45 to 65 Hz)

Current Limit

115% maximum

Output

Voltage

208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 4 w + Gnd

Frequency

50/60 Hz ± 0.01% (Can be Used as a Frequency Converter)

Voltage Regulation

< 1% balanced, 100% load step; < 2% unbalanced, 100% load step

Overload (inverter)

125% for 90 sec, 150% for 30 sec

Overload (bypass)

125% for 10 min, 1,000% for 10 ms

Battery 

DC Link

288 VDC

Ripple Voltage 

<.5% DC

Environment

Temperature Range

0 to 40°C (operating)/-20 to +50°C (storage)

Relative Humidity

0 to 95% non condensing

Heat Rejection

5,733 BTUs

7,600 BTUs

9,100 BTUs

17,737 BTUs

24,270 BTUs

Efficiency

AC/DC/AC 87.7%, DC/AC 90%

AC/DC/AC 88.5%

AC/DC/AC 90%

Dimensions

Dimensions (L x D x H)

20” x 36.3” x 59.8”

35.6” x 37.6” x 59.8”

44” x 31” x 74”

(1 / 2) Transformer(s)

UPS Weight (lb) 

1,275/1,475

1,275/1,475

1,275/1,475

1,581/1,941

2,450

Altitude 

6,600 ft (2000 m) (Maximum Without Derating)

Audible Noise

< 60 dBA at 1 m

< 65 dBA  at 1 m

< 65 dBA  at 1 m

Features

Internal Make-before-break Maintenance Bypass Switch*, RS232 and Dry Contact Interface

Options

Dual Input Feed, Air Filters for Door, RemotEye II

®

Standards

UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993

Warranty

 (See Toshiba Warranty Policy for Full Details.)

Service

7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3) 

Reviews: