4200FA Installation and Operation Manual
89
The audible alarm can be disabled permanently by selecting the Settings tab, then setting the parameter
808 -
Buzzer
to “Disable.” This will disable the alarm so that no alarm sounds for any Fault or Warning
condition.
Initial Battery Charge
10.6
The UPS Battery System must be charged before it is used for the first time or when the unit has not
been used (AC power source removed) for more than 10 days. The batteries can be charged in Online
Mode, but the full backup capacity will require up to 24 hours of uninterrupted charging. Use the following
procedure to recharge the UPS Battery System:
1) Ensure the UPS key switch is in the “BYPASS” position.
2) Switch on power at the UPS input distribution panel, and battery disconnects.
3) Switch the MAIN POWER SWITCH on the inner front panel to "ON." The UPS battery charging
circuit is now activated. The AC ON LED will be green. The
MAIN
Tab will display on the
Touchpad
4) With the key switch in the BYPASS position, the AC IN and the BYP LED’s will be lit.
Press the touchscreen menu STATUS tab. The mimic display should show the power being
routed through the MBS (Heavy Line)
5) Turn the Key Switch to “RUN”.
If parameter 527 -
Battery Test
is set to “Enable”, the UPS automatically performs a controlled
system battery test. (Note: The Automatic Battery Test.is performed only when the software is
enabled for this function. The factory default is set to “Disable.”)
(Allow 24-72 hours for the batteries to fully charge)
.
Use the following procedure if the automatic battery test fails and the “low battery” warning
VBLO
is
displayed in the touchscreen footer (Figure 4-2):
1) Turn the key switch to “Bypass.”
2) Allow 24-72 hours for the batteries to charge and then switch the Circuit Breaker to "OFF."
3) Repeat Initial Battery Charge procedure. (A failure indicates battery replacement may be
necessary).
Start-up Procedure
10.7
The UPS batteries must be charged before the UPS is used for the first time or if the unit has not been
used (i.e. AC power source removed) for more than 10 days. Once the batteries are charged use the
following start-up procedure:
1) Verify that all power switches are off, and that the "BYPASS/RUN” Switch on the UPS is in the
“BYPASS” position.
2) Switch on the power at the customer-provided UPS input distribution panel.
3) Switch the UPS Circuit Breaker(s) to "ON." The AC Input LED will light. The touchscreen should
display the MAIN tab:
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......