4200FA Installation and Operation Manual
119
Blk
Item
Long Description
Short Description
(Inside UPS)
Units
Permissions
Remark
RE
III
User
Admin
3
40
No of Bypass Line
No of Bypass Line
R
R
Y
3
47
Bypass UV Detection Level
VbUV DeLevel
%
R
R
Y
3
49
Bypass OV Detection Level
VbOV DeLevel
%
R
R
Y
4
1
DC Bus Total
DC Bus Total
Vdc
R
R
Y
5
1
Battery Voltage
Battery Voltage
Vdc
R
R
Y
5
3
Battery Discharge Current
Discharge Current
Adc
R
R
Y
5
12
Equalized Setting
Auto Equal Ch
R
R/W
N
5
13
Equalized Charge Time
Equal Charge Time
R
R/W
Y
5
14
Float Charging Voltage
Vchrg Float
Vdc
R
R/W
Y
5
22
Low Battery Detection Level
Low Batt Level
Vdc
R
R
Y
5
24
Battery Shutdown Level
Batt SDown Level
Vdc
R
R
Y
5
26
Manual Battery Test
Manual Batt Test
R/W
R/W
Enable
- Start Battery Test
Disable
- No Action
If battery test:
Pass Test
- No Message, backup
record will record successful batt
test.
Fail Tes
t - Displays VBLO or VBSD
message with warning LED and
Buzzer.
N
5
27
Auto Battery Test
Auto Batt Test
R
R/W
Y
5
28
Battery Auto Test Interval
Auto Test Interval
Sec
R
R/W
Y
5
29
Battery Test at Startup
Batt Test @startup
R
R/W
Y
5
30
Equalized Power Failure Duration
PFail Dur. Equal
Sec
-
R/W
Y
5
31
Number of Batteries in Series
No Batt(Series)
R
R/W
Y
5
32
Number of Batteries in Parallel
No Batt(Paral)
R
R/W
Y
5
33
Rated Ampere Hour
Rated AHr
R
R/W
Y
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......