15 kVA
25 kVA
30 kVA
50 kVA
Rated Output
Rating
Rating
Rating
Rating
240 VAC
240 V, 45 A
240 V, 80 A
240 V, 90 A
240 V, 150 A
380/220 VAC
480 V, 30 A
480 V, 50 A
480 V, 60 A
480 V, 100 A
480/277 VAC
480 V, 25 A
480 V, 40 A
480 V, 45 A
480 V, 80 A
600 VAC
600 V, 20 A
600 V, 30 A
600 V, 40 A
600 V, 60 A
The maximum ambient temperature in which the Uninterruptible Power System (UPS) should be operated
is 104
°
F (40 °C) without batteries and 89
°
F (32 °C) if the battery cabinet is subject to the same ambient
temperature as the UPS. The nominal battery voltage for all internal battery models is 288 VDC. The
nominal battery voltage for all external battery models is 288 VDC.
An Authorized TOSHIBA Representative who is knowledgeable of batteries and the required precautions
should perform service on the batteries. Keep unauthorized personnel away from batteries.
Refer to the Battery System Manual when scheduling battery maintenance or battery replacement.
DANGER
Misuse of this equipment could result in injury and equipment damage.
In no event will TOSHIBA be responsible or liable for direct,
indirect, or consequential damage or injury that may result from the misuse of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may
explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is toxic and
harmful to the eyes and skin.
CAUTION
This unit contains sealed lead acid batteries. An annual preventative
maintenance should be performed by an authorized technician.
Failure to do so could result in batteries exploding and emitting gasses.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is toxic and
harmful to the eyes and skin.
WARNING
Failure to replace a battery before it becomes exhausted may cause
the case to crack, possibly releasing electrolytes from inside the
battery, and resulting in secondary faults such as odor, smoke, and
fire.
WARNING
Only personnel knowledgeable of batteries and the required
precautions should perform installation and servicing of batteries.
Keep
Unauthorized personnel away from the batteries.
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......