14
4200FA Installation and Operation Manual
Unpack the Base and Seismic 50 kVA UPS (without Casters)
4.4
•
4200FA 50kVA Base (P/N T42F3F500XAXXN , T42F3F500XAXBN)
•
4200FA 50kVA Seismic (P/N T42F3F500XAMX0S)
Upon receipt of the UPS, a careful inspection for shipping damage should be made. Units shipped within
North America and NAFTA are shrink-wrapped; those outside North America are crated.
1. Remove the shrink wrap from the UPS and Pallet.
2. Unbolt the UPS from the shipping pallet.
3. Position the forks between the C-channel feet on the bottom of the 50kVA UPS cabinet. (front or
back access)
4. Lift the UPS off the pallet.
5. Use the forklift/floor jack to position the UPS on the pre-drilled mounting holes. See Section 2.7
Seismic Version has two outer and a center C-channel skid
Base Version has two outer C-channel skids but NO center skid
DANGER
TOP HEAVY EQUIPMENT – DO NOT tilt the UPS more than 10
°
from the
upright position.
Tilting the UPS more than 10
°
may cause crushing, trapping, or other
personal injuries and cause physical damage to internal components.
THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE.
Center C-channel skid
(Seismic version only)
Figure 4-1 Offload 50kVA UPS (No Casters)
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......