22
4200FA Installation and Operation Manual
Table 6.1 Cable Size for Different 3P-3W I/O Voltages
Minimum / Maximum Wire Size and Torque requirements
UPS Input/Bypass Terminals
TB1
15-30 kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Input/
Bypass:
(L1) (L2)
(L3) (N)
15 kVA
25 kVA
30 kVA
AWG
(L1) –
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
120/208 V
6 – 1
4 – 1
51
51
3 – 1
1
51
87
2 – 1
1
87
87
208 V
6 – 1
N/A
51
N/A
3 – 1
N/A
51
N/A
2 – 1
N/A
87
N/A
220 V
6 – 1
N/A
51
N/A
4 – 1
N/A
51
N/A
2 – 1
N/A
87
N/A
240 V
8 – 1
N/A
51
N/A
6 – 1
N/A
51
N/A
2 – 1
N/A
87
N/A
380 V
10 – 1
N/A
35
N/A
6 – 1
N/A
51
N/A
6 – 1
N/A
51
N/A
400 V
10 – 1
N/A
35
N/A
6 – 1
N/A
51
N/A
6 – 1
N/A
51
N/A
415 V
10 – 1
N/A
35
N/A
6 – 1
N/A
51
N/A
6 – 1
N/A
51
N/A
480 V
10 – 1
N/A
35
N/A
8 – 1
N/A
51
N/A
6 – 1
N/A
51
N/A
600 V
10 – 1
N/A
35
N/A
10 – 1
N/A
35
N/A
10 – 1
N/A
35
N/A
Table 6.2 Cable Size for 3P-4W I/O Voltages
Output:
(L1) (L2)
(L3) (N)
15 kVA
25 kVA
30 kVA
AWG
(L1) –
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
120/208 V
6 – 1
4 – 1
51
51
3 – 1
1
51
87
2 – 1
1
87
87
127/220 V
6 – 1
4 – 1
51
51
3 – 1
1
51
87
2 – 1
1
87
87
240 V
6 – 1
N/A
51
N/A
3 – 1
N/A
51
N/A
2 – 1
N/A
87
N/A
220/380 V
10 – 1
8 – 1
35
51
8 – 1
4 – 1
51
51
6 – 1
2 – 1
51
87
230/400 V
10 – 1
8 – 1
35
51
8 – 1
4 – 1
51
51
6 – 1
2 – 1
51
87
240/415 V
10 – 1
8 – 1
35
51
8 – 1
4 – 1
51
51
6 – 1
2 – 1
51
87
277/480 V
10 – 1
8 – 1
35
51
8 – 1
6 – 1
51
51
6 – 1
2 – 1
51
87
600 V
10 – 1
N/A
35
N/A
10 – 1
N/A
35
N/A
10 – 1
N/A
35
N/A
Table 6.3 Cable Size for Ground
Input/ Bypass/ Output
(GND)
15 kVA
25 kVA
30 kVA
AWG*
Torque
AWG*
Torque
AWG*
Torque
(G)
10 – 1
35 in-lbs.
8 – 1
51 in-lbs.
6 – 1
51 in-lbs.
*Maximum Wire Size is 1 AWG.
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......