4200FA Installation and Operation Manual
23
Table 6.4 Bypass Wire Size
Minimum / Maximum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input
TB4
15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
15 kVA
25 kVA
30 kVA
AWG*
Torque
AWG*
Torque
AWG*
Torque
208 V
8 – 1
51 in-lbs.
4 – 1
51 in-lbs.
2 – 1
87 in-lbs.
220 V
8 – 1
51 in-lbs.
4 – 1
51 in-lbs.
2 – 1
87 in-lbs.
240 V
8 – 1
51 in-lbs.
4 – 1
51 in-lbs.
2 – 1
87 in-lbs.
380 V
10 – 1
35 in-lbs.
8 – 1
51 in-lbs.
6 – 1
51 in-lbs.
400 V
10 – 1
35 in-lbs.
8 – 1
51 in-lbs.
6 – 1
51 in-lbs.
415 V
10 – 1
35 in-lbs.
8 – 1
51 in-lbs.
6 – 1
51 in-lbs.
480 V
10 – 1
35 in-lbs.
8 – 1
51 in-lbs.
6 – 1
51 in-lbs.
600 V
10 – 1
35 in-lbs.
10 – 1
35 in-lbs.
10 – 1
35 in-lbs.
*Maximum Wire Size is 1 AWG.
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......