4200FA Installation and Operation Manual
29
6.3.1
Recommended Wire Size and Torque Requirements for 50kVA
Minimum wire sizes are based on NEC Table 310.16. Neutral wire is sized per NEC Article
310.15(B), Grounding wires sized per NEC Article 250.122. Maximum wire capacity of the power
terminal lugs is 250kcmil.
Table 6.7 50kVA Cabling Sizes
Minimum / Maximum Wire Size and Torque Requirements
UPS Input and Output Terminals
TB1
50 kVA*
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
INPUT:
OUTPUT:
(H1) (H2)
(H3)
AWG
NEUTRAL
AWG
(L1)(L2)
(L3)
AWG
NEUTRAL
AWG **
Tightening
Torque
208 V
2/0 – 250 kcmil
250 kcmil
208/120 V
2/0 – 250 kcmil
250 kcmil
200 in-lbs.
220 V
2/0 – 250 kcmil
4/0 – 250 kcmil
220/127 V
2/0 – 250 kcmil
4/0 – 250 kcmil
200 in-lbs.
240 V
2/0 – 250 kcmil
N/A
240 V
1/0 – 250 kcmil
N/A
200 in-lbs.
380 V
2 – 250 kcmil
1/0 – 250 kcmil
380/220 V
4 – 250 kcmil
1/0 – 250 kcmil
200 in-lbs.
400 V
3 – 250 kcmil
1/0 – 250 kcmil
400/230 V
4 – 250 kcmil
1/0 – 250 kcmil
200 in-lbs.
415 V
3 – 250 kcmil
1 – 250 kcmil
415/240 V
4 – 250 kcmil
1 – 250 kcmil
200 in-lbs.
480 V
4 – 250 kcmil
2 – 250 kcmil
480/277 V
6 – 250 kcmil
1 – 250 kcmil
200 in-lbs.
600 V
6 – 250 kcmil
N/A
600 V
6 – 250 kcmil
N/A
200 in-lbs.
Table 6.8 Bypass Cabling Sizes
Minimum / Maximum Wire Size and Torque requirements
UPS Optional Bypass Input Terminals
TB4
50 kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C) (N)
Input: (H1) (H2) (H3)
50 kVA
AWG*
NEUTRAL AWG*
Tightening Torque
208/120 V
1/0 – 250 kcmil
250 kcmil
200 in-lbs.
220 V
1/0 – 250 kcmil
250 kcmil
200 in-lbs.
240 V
1/0 – 250 kcmil
N/A
200 in-lbs.
380 V
2 – 250 kcmil
2/0 – 250 kcmil
200 in-lbs.
400 V
3 – 250 kcmil
2/0 – 250 kcmil
200 in-lbs.
415 V
3 – 250 kcmil
1 – 250 kcmil
200 in-lbs.
480 V
4 – 250 kcmil
2 – 250 kcmil
200 in-lbs.
600 V
6 – 250 kcmil
N/A
200 in-lbs.
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......