4200FA Installation and Operation Manual
6.4.1
Recommended Wire Size and Torque Requirements
UPS Control and Battery Interface 50 kVA wire and torque requirements.
Table 6.12 TB-3 Tightening Torque
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75 °C COPPER WIRING
TERMINAL
(TERMINAL #)
50 kVA
AWG*
TIGHTENING
TORQUE
UPS CONTROL CIRCUITS
(1-24)*
14-16
8 in-lbs.
BATTERY CONTROL
CIRCUITS (3-6)*
14-16
8 in-lbs.
*Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG.