44
4200FA Installation and Operation Manual
4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output - No Internal Batteries, No Internal
7.4
Transformer
Model Number
T42F3F300XAXXN
T42F3F300XAMXN, -S
T42F3F300FAMXN, -S
Rated Output Capacity
30 kVA
External Dimensions
W x D x H (cm)
w/ casters: 20.0” x 36.3” x 59.7”(50.8 cm x 92.2 cm x 151.6 cm)
w/o casters: 20.0” x 36.3” x 60.0”(50.8 cm x 92.2 cm x 152.4 cm)
Input
Rated Voltage
208 VAC
Voltage Variation
4,5
+10% to -15%; (-10% to -15%)
4
, (-15 to -30%)
5
Rated Frequency
50 / 60 Hz
Input Cables required
3 phase ; 4 Wire + GND
Dual Input Option Cables required
3 phase ; 4 Wire + GND
Power Factor
1
Greater than 0.98 when in inverter mode
1
Required Input kVA
28.0 kVA
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times the rated current under synchronous operation
Current Limit
115% maximum
Harmonic Currents
1
Less than 3% THD
1
Battery
DC Nominal (Voltage Range)
288 VDC (216 to 332 VDC)
Float Charge (Regulation)
324.0 VDC (
±
2%)
Ripple Voltage
0.5 V R.M.S.
Rated Back-up Time
2
Refer to Battery System Manual
Rated Charge Current
10.0 Amps
Output
Rated Voltage
208 / 120 VAC
Rated Current
83.4 Amps
Rated Power Factor
0.8 lagging
Output Cables Required
3 phase ; 4 Wire + GND
Voltage Regulation (phase-phase)
±
2% (0 – 100% balanced load);
±
3% (0 – 100% unbalanced load)
Voltage Adjustment Range
±
5V Manually from the key pad
Phase Displacement
±
2
°
(0 – 100% balanced load);
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
±
0.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
Voltage Transients
(Recovery time: 50 ms)
±
5% (100% load step change);
±
3% (loss or return of input voltage);
±
8% (transfer of bypass to inverter)
Inverter Overload Capacity
125% for 90 sec; 150% for 30 sec
Bypass Overload Capacity
1000% for 10 ms; 125% for 10 min.
Crest Factor
2.5 – 3.0 within the kW range
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......