56
4200FA Installation and Operation Manual
7.10.2 Efficiency with Input Transformer
4200FA Series
15 kVA w/ 1 Xfmr
25 kVA w/1 Xfmr
3 kVA w/1 Xfmr
50 kVA w/ 1Xfmr
100% Load *
86.5%
88.2%
86.5%
86.5%
*Contact the factory for additional information on efficiency vs. load curves.
7.10.3 Thermal Loss in BTU/Hr. with Input Transformer
4200FA Series
15 kVA w/ 1 Xfmr
25 kVA w/1 Xfmr
30 kVA w/1 Xfmr
50 kVA w/ 1Xfmr
100% Load
6390
9130
12,781
21,301
75% Load
5250
7112
9915
16,802
50% Load
4403
5417
7857
13,878
25% Load
3449
4106
6430
8961
0% Load
2,730
4,077
4,892
6,403
7.10.4 Efficiency with Input and Output Transformer
4200FA Series
15 kVA w/ 2 Xfmr
25 kVA w/2 Xfmr
30 kVA w/2 Xfmr
50 kVA w/ 2 Xfmr
100% Load *
85.1%
86.7%
85.1%
85.8%
*Contact the factory for additional information on efficiency vs. load curves.
7.10.5 Thermal Loss in BTU/Hr. with Input and Output Transformers
4200FA Series
15 kVA w/ 2 Xfmr
25 kVA w/2 Xfmr
30 kVA w/2 Xfmr
50 kVA w/ 2 Xfmr
100% Load
7169
10,468
14,338
22,588
75% Load
5893
8125
11,904
17,641
50% Load
4833
6069
8746
14,567
25% Load
3691
4481
6897
9290
0% Load
2730
4,077
4,892
6,403
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......