4200FA Installation and Operation Manual
Bypass Mode
8.2
If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched from the
main circuit to the Bypass circuit. Power flow through the bypass is shown in the following illustration.
This changeover occurs automatically in less than 4 milliseconds in phase (Make-Before-Break).
If the power flow is transferred to the Bypass circuit because of an overload, and that overload condition ends within a
specified period of time, then the power flow will "re-transfer" to the AC Input Mode (Normal Operation) automatically.
If the power flow is transferred to the Bypass circuit due to a fault condition, then the power flow must be
transferred manually from the UPS's Bypass circuit back to the Inverter circuit after repairing the fault
(see
"Start-up Procedure").
If the power flow is transferred to the Bypass circuit due to an overload condition, then the power flow will
automatically transfer from the UPS's Bypass circuit back to the Inverter circuit after removing the overload
(see "Overload Operation").
Figure 8-2 Power Flow in Bypass Mode
Input
Power
Converter
Inverter
Bypass
Charger/
Chopper
Isolating
XFMR
External
Batteries
Output
Power
MCCB
MBS
(Not available for LT units)
Power Flow
Summary of Contents for 4200FA Series
Page 2: ...4200FA Installation and Operation Manual ...
Page 12: ...vi 4200FA Installation and Operation Manual ...
Page 16: ...4 4200FA Installation and Operation Manual NOTE This Label for Battery Units Only ...
Page 110: ...98 4200FA Installation and Operation Manual 36 3 in 922 mm ...
Page 115: ...4200FA Installation and Operation Manual 103 APPENDIX A Seismic Anchorages ...
Page 116: ...104 4200FA Installation and Operation Manual ...
Page 117: ...4200FA Installation and Operation Manual 105 ...
Page 118: ...106 4200FA Installation and Operation Manual ...
Page 136: ...124 4200FA Installation and Operation Manual ...
Page 137: ......