61
4300 Series Installation and Operation Manual
LB
Low Battery – The battery voltage has dropped
low (about 90% or less) during operation. Contin-
ued operation in this mode will deplete battery and
cause output shut down. (This can be adjusted by
the operator
Immediately shut down the load
equipment in an orderly fashion
and then press the STOP key.
LCRUN
Local run command issued.
No action needed.
MANUAL
UPS is in Manual mode
No action needed.
OUT50HZ
UPS set for 50 Hz Output.
No action needed.
PFAIL
Input power failure.
No action needed.
PRCHRG
Protective charging
No action needed.
RMRUN
Remote Run command issued.
No action needed.
RMTSD
Remote shutdown occurred.
One or more warnings occurred.
Check the Warnings field for
details. Disconnect LAN signal
to reset.
RMTSWEN
Remote switch control enable.
No action needed.
SYN
Synchronous mode.
Input and output are synchro-
nized.
TIMEDSD
UPS is counting down prior to shutdown.
Immediately shut down the load
equipment in an orderly fashion
and then press the STOP key.
WRN
A warning has occurred.
See Warning record.