4300 Series Ancillary Cabinets Installation and Operation Manual
8.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 8.2 for anchor bolt installation detail.
Use 1/2” (12 mm) diameter anchor bolts. There are four 0.63” (16 mm) diameter holes provided in the
cabinet base. See Figure 8.3A for the hole locations and dimensions for the specified Ancillary Cabinets..
Anchor Bolt
(1/2 in (12 MM))
4 x 0.63 in. (16 mm)
diameter bolt holes
4 bolt holes
(Side View)
FIGURE 8.2 ANCHOR BOLT INSTALLATION DETAIL
FIGURE 8.3A HOLE LOCATIONS/DIMENSIONS ON BOTTOM OF CABINETS
431A/431B
Back
Front
4 x 0.63 in. Dia. (16 mm)
19.0 in. (483 mm)
26.7 in..
(677 mm)
431M
Back
Front
11.0 in. (279 mm)
20.0 in.
(508 mm)
4 x 0.63 in. Dia. (16 mm)
FIGURE 8.3B HOLE LOCATIONS/DIMENSIONS ON SIDES OF CABINETS
A
B
Left Side
A
B
Right Side
Dimensions
A - 29 in. (736 mm)
B - 60 in. (1523 mm)
Use 4 ea. 3/8”x16 2 in
long bolts to join adjacent
UPS /ancillary cabinet
frames.
(The left side
of each cabinet has a
3/8”x16 pin nut to receive
the corresponding bolt.)