TD - Series
- 17 -
TD Series
Digital Solid State Soft Starter 48 - 1250A
5.4 The TD Function List
5.4.1 Motor FLA, Service Factor and Overload Protection Functions
5.4.2 Starting Mode Functions
5.4.3 Jog Mode Functions
Note 1: Current percentages are based on Motor Full Load Amps (FLA) as entered in F001.
Fn
Group
Function
Adjustment
Range
Setting
Increments
Factory
Setting
Section
F001
Motor Nameplate FLA
Motor FLA must be programmed
for proper unit operation.
50-100% of starter Max. Amp rating
Upper limit of range automatically
adjusts downward as Service
Factor is increased
1 amp
0
(Starter disabled
until set to FLA)
5.5.1
F002
Motor Nameplate Service Factor
1.00 - 1.30
0.05
1.0 SF
5.5.1
F003
Overload Class During Start
5 - 30 NEMA / UL Class
Overload Time / Trip Curve
5
Class 10
5.5.1
F004
Overload Class During Run
5 - 30 NEMA / UL Class
Overload Time / Trip Curve
5
Class 10
5.5.1
F005
Overload Reset
0=Manual
1=Auto
2=Disabled Overload
1
0 (Manual)
5.5.1
5.5.1
F006-
F009
Reserved
Reserved
Reserved
Reserved
Motor
and O
verl
oad
Fn
Group
Function
Adjustment
Range
Setting
Increments
Factory
Setting
Section
F010
Ramp Select
VR = Voltage Ramp,
CR = Current Ramp
Range is 1 - 4
Setting to #1: Ramp 1 = VR, Ramp 2 = VR
Setting to #2: Ramp 1 = CR, Ramp 2 = CR
Setting to #3: Ramp 1 = VR, Ramp 2 = CR
Setting to #4: Ramp 1 = CR, Ramp 2 = VR
1
1 (VR1-VR2)
5.5.2
F011
Initial Voltage of Ramp 1
0-100%
1%
60%
5.5.2
F012
Initial Current of Ramp 1
0-600% (note1)
1%
200%
5.5.2
F013
Accel Ramp Time of Ramp 1
1-120 seconds
1 second
10 seconds
5.5.2
F014
Max Current Limit of Ramp 1
200 - 600% (note1)
1%
350%
5.5.2
F015
Initial Voltage of Ramp 2
0-100%
1%
60%
5.5.2
F016
Initial Current of Ramp 2
0-600% (note1)
1%
200%
5.5.2
F017
Accel Ramp Time of Ramp 2
1-120 seconds
1 second
10 seconds
5.5.2
F018
Max Current Limit of Ramp 2
200 - 600% (note1)
1%
350%
5.5.2
S
tart
ing
Mode
Fn
Group
Function
Adjustment
Range
Setting
Increments
Factory
Setting
Section
F019
Voltage Jog
5 - 100%
1%
50%
5.5.3
F020
Time of Voltage Jog
1 - 20 Seconds
1 second
10 seconds
5.5.3
F021
Current Jog
100 - 500%
1%
150%
5.5.3
Jog
Mod
e