5.4.10 Fault History and Run Time
5.5 Function Descriptions
The unit is set at the factory with typical starting characteristics that perform well
in most applications.
Note: Customer must program motor FLA (F001) for unit to operate.
5.5.1 Motor and Overload Function Descriptions
F001 = Motor FLA
Factory Setting = 0
Range = 50 - 100% of Unit Max. Current.
Set the value of this function to the motor nameplate Full Load Amps
(FLA). Adjustments for service factor are not necessary when
programming this function. (See note below). If the motor nameplate
FLA is not available, use typical values as shown in NEC, NEMA
standard MG-1 or other reputable third party source (motor manufacturer,
etc.).
Note:
To prevent adjusting the settings beyond the starter Max Amp rating, the range
of adjustment for the Motor Nameplate FLA will vary to reflect the Service
Factor as programmed into F002. At the default setting of 1.0SF, the full range
of adjustment from 50 - 100% of the Max Amp rating is available. For example
F002 = 1.15 to reflect a 1.15SF, the maximum FLA programmable into F001 will
be limited to 85% of the starter Max. Amp rating (100% - 15%).
Fn
Group
Function
Adjustment
Range
Setting
Increments
Factory
Setting
Section
F075
Fault History #1, Latest Fault
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
View Only
0
5.5.10
F076
Time Stamp, Fault #1
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
View Only
00.00 EST
5.5.10
F077
Date Stamp, Fault #1
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
View Only
01.01
5.5.10
F078
Fault History #2,
Previous Fault
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
View Only
0
5.5.10
F079
Time Stamp, Fault #2
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
View Only
00.00 EST
5.5.10
F080
Date Stamp, Fault #2
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
View Only
01.01
5.5.10
F081
Fault History #3, Oldest Fault
0, 1 - 27 (Fault #: see Fault
code list; 0: No fault history)
View Only
0
5.5.10
F082
Time Stamp, Fault #3
00.00-23.59 (hh.mm)
[hh = 00-23; mm = 00-59]
View Only
00.00 EST
5.5.10
F083
Date Stamp, Fault #3
01.01 - 12.31 (MM.DD)
[MM = 01-12; DD = 01-31]
View Only
01.01
5.5.10
F084
Run Time, Hours
000.0 - 999.9 (hours)
View Only
0
5.5.10
F085
Run Time, K Hours
0000 - 9999 (thousand hours)
View Only
0
5.5.10
F086
Run Counts
0000 - 9999 (times)
View Only
0
5.5.10
F087
Run Counts, 10K times
0000 - 9999 (10 thousand times)
View Only
0
5.5.10
Fau
lt H
istor
y and R
un Ti
me